background image

VALVE TERMINALS 

GAS CONTROL KNOB 

PIEZO IGNITOR

 

HI /LO FLAME ADJUSTMENT KNOB 

ON/OFF ROCKER SWITCH 

ELECTRODE 

PILOT HOOD 

THERMOPILE 

THERMOCOUPLE 

PILOT SHIELD 

   55345 VALVE & PILOT ASSEMBLY COMPONENTS  

PAGE 38 

 

Содержание MINNETONKA 55345-RF

Страница 1: ...you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If the information in these i...

Страница 2: ......

Страница 3: ...ourselves in being dedicated to not only function and reliability but customer safety as well We offer our continual support and guidance to help you achieve the maximum benefit and enjoyment from you...

Страница 4: ......

Страница 5: ...21 800 WPT Wall Pass Thru Installation Instructions 22 VENTING cont Horizontal Min Max Venting Illustrations 23 24 Vertical Vent System Clearances 25 Combustion Air Intake Settings 25 Horizontal Verti...

Страница 6: ...appliance should be located out of traffic and away from furniture and draperies The glass front or any part removed for servicing the appliance must be replaced prior to operating the appliance Work...

Страница 7: ...or thermostat remote control Wall mount thermostat wireless wall mount thermostat Decorative full door faces in various styles and finishes Renaissance pattern front Mission design doors in various f...

Страница 8: ...eet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print no less the one half inch 1 2 in size...

Страница 9: ...26 1 2 10 18 1 2 32 5 8 10 1 4 MILLIMETERS 876 1038 743 543 902 673 254 470 829 260 SPECIFICATIONS WARNING NON COMBUSTIBLE ZONE STAND OFFS PROVIDE THE 10 254 mm MINIMUM CLEARANCE TO HEADER USE ONLY NO...

Страница 10: ...LY NON COMBUSTIBLE MATERIAL IN THIS AREA FOR THE ENTIRE WIDTH OF FIREPLACE DO NOT USE WOOD SHEETROCK ETC IN THIS ZONE NOTE OTHER CLEARANCES APPLY ALL CLEARANCES MUST BE MAINTAINED REFER TO PAGE 14 FOR...

Страница 11: ...ustible surface not linoleum or carpet extending the entire depth and width of fire place Due to high surface temperatures fireplace should be located out of traffic and away from furniture and draper...

Страница 12: ...NT THE TOP STAND OFF BRACKETS MUST BE FORMED AND ATTACHED PRIOR TO POSITIONING THE FIREPLACE INTO FRAMED OPENING WARNING NON COMBUSTIBLE ZONE STAND OFFS PROVIDE THE 10 254 mm MINIMUM CLEARANCE TO HEAD...

Страница 13: ...MUST BE INSTALLED WHEN USING A 45 DEGREE ELBOW TO HORIZONTALLY POSITION THE VENT SYSTEM EXCEPTION CORNER INSTALLATIONS To Install Horizontal Vent Heat Shield Attach here Tighten screws NAILING FLANGE...

Страница 14: ...doors full door faces access the control valve installation of gas line fan etc PAGE 11 WARNING DO NOT OBSTRUCT UPPER AND LOWER GRILL OPENINGS ROOM AIR ENTERS THROUGH THE LOWER PASSAGE IS HEATED AND...

Страница 15: ...the full width and depth of fireplace Minimum plat form size 44 7 8 1038 mm wide x 21 3 8 543mm deep FIRE HAZARD Do NOT install directly on carpeting vinyl or any combustible material other than wood...

Страница 16: ...HE VENT SYSTEM EXCEPTION CORNER INSTALLATIONS TYPICAL INSTALLATION OPTIONS TYPICAL CORNER INSTALLATION TYPICAL VERTICAL INSTALLATION TYPICAL HORIZONTAL INSTALLATION NOTE HORIZONTAL VENT HEAT SHIELD NO...

Страница 17: ...header of fireplace 800 series flexible venting 1 25 mm above elbow for entire width and depth behind header of fireplace NON COMBUSTIBLE ZONE 10 254mm 15 381mm 17 432mm 19 483mm 10 254mm 12 305mm 14...

Страница 18: ...front B Pull top handles out and down to secure glass frame assembly top C Pull bottom handles out and up to secure glass frame assembly bottom CAUTION TO PREVENT GLASS FRAME ASSEMBLY FROM FALLING OF...

Страница 19: ...embly Refer local electrical codes for specific requirements WARNING THIS APPLIANCE IS EQUIPPED WITH A THREE PRONG GROUNDING PLUG FOR PROTECTION AGAINST SHOCK HAZARD AND SHOULD BE PLUGGED DIRECTLY INT...

Страница 20: ...er grill upper louver upper hood Refer to page 37 of this installation manual if necessary Before adjusting the temperature control switch unplug the 3 prong plug on the fan cord from the receptacle A...

Страница 21: ...m control valve inlet If substituting for these components please consult local codes for compliance NOTE This fireplace is equipped with a 3 8 10 mm x 18 457 mm long flexible gas connector and manual...

Страница 22: ...000 40 000 MINIMUM INPUT BTU hr 21 500 26 500 EFFICIENCY 69 73 AFUE 68 72 P 4 AFE 66 63 55345 NATURAL GAS LP GAS MINIMUM INLET GAS PRESSURE 5 0 inches W C 7 0 W C recommended 11 0 inches W C recommend...

Страница 23: ...trol IMPORTANT The insulated cover included with the remote control must be placed over the remote receiver to prevent overheating IMPORTANT If ON OFF rocker switch wires are not disconnected the ON O...

Страница 24: ...NTING NOTE 2 45 degree elbows may be used in place of 1 90 elbow HORIZONTAL TERMINATIONS MINIMUM 45 elbow 6 152 mm horizontal termination cap MAXIMUM U S Installations 45 elbow 10 ft 3 05 m terminatio...

Страница 25: ...pass thru section marked 1 with 3 8 10 mm flange into framed opening Secure to interior wall with screws not provided C From the exterior place insulation between flange and top of framed opening in...

Страница 26: ...allation Page 51 has information on restrictor recommendations depending on burner flame appearance and instructions on installation after venting is completed TERMINATION CAP MINIMUM HORIZONTAL VENTI...

Страница 27: ...nstallation in conjunction with venting installation Page 51 has information on restrictor recommendations depending on burner flame appearance and instructions on installation after venting is comple...

Страница 28: ...ter venting is completed RESTRICTOR VERTICAL VENT SYSTEM CLEARANCES TOP BOTTOM SIDES DURA VENT 1 inch 25 mm 1 inch 25 mm 1 inch 25 mm AMERI VENT 1 inch 25 mm 1 inch 25 mm 1 inch 25 mm ICC EXCELDirect...

Страница 29: ...ecommendations depending on burner flame appearance and instructions on installation after venting is completed MAXIMUM VERTICAL VENTING MINIMUM VERTICAL VENTING 45 ELBOW TERMINATION CAP TERMINATION C...

Страница 30: ...ding on burner flame appearance and instructions on installation after venting is completed Horizontal sections require 1 4 6 mm rise for every 12 305 mm of travel For each additional elbow used after...

Страница 31: ...n on restrictor recommendations depending on burner flame appearance and instructions on installation after venting is completed IMPORTANT The Kozy Heat wall pass thru part 800 WPT or 800 WPT2 must be...

Страница 32: ...the four slots B securing it in place 9 Gently pull 5 8 pipes down to the top of extension kit or top of fireplace if no extension kits were used 10 Place a bead of sealant outside 5 flex pipe collar...

Страница 33: ...ft 914 mm horizontally from the centerline of the regulator I Gas Service regulator vent outlet 3 ft 914 mm J Non mechanical air supply inlet to building or the combustion air inlet to any other appl...

Страница 34: ...ROOF PITCH X 12 H minimum MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING APPROVED CAP APPROVED VENT PIPE DISCHARGE OPENING 8 MIN IF VENT IS CLOSER THAN 8 IT MUST TERMINATE AT LEAST 2 HIGHER THA...

Страница 35: ...TION Do not place logs directly over burner port holes Improper log placement may affect flame appearance and cause excessive soot to build up on logs and glass STEP 2 PAGE 32 STEP 1 1A Position base...

Страница 36: ...ON PAGE 33 STEP 4 STEP 3 11 4A Position log 4A as shown above Install 11 log over burner jumper tube 10A 9A 8A Position logs 7A 10A onto base logs aligning holes in logs to the protrusions on base log...

Страница 37: ...his area Do not place Klinkers directly on burner ports Use a steel or stiff bristle nylon brush to distribute Rock Wool Embers onto logs and burner 12A Align notch in log 12A to the log grate while p...

Страница 38: ...pilot shield and ember log refractory 8 Remove pilot shield 9 Remove screws securing front left and back right log grate legs Remove burner log grate assembly from firebox by lifting front of burner...

Страница 39: ...ember refractory 7 Reinstall log set Pages 32 34 8 Reconnect gas line to manual shut off valve 9 Model 55345 Reconnect any wall switch remote control or thermostat wires to the top bottom terminals o...

Страница 40: ...ps PAGE 37 Thread screws into nuts on each end of grill and secure to lower grill opening UPPER LOUVER HOOD LOWER GRILL INSTALLATION REMOVAL INSTALLATION REMOVAL C Partially thread the 2 screws includ...

Страница 41: ...VALVE TERMINALS GAS CONTROL KNOB PIEZO IGNITOR HI LO FLAME ADJUSTMENT KNOB ON OFF ROCKER SWITCH ELECTRODE PILOT HOOD THERMOPILE THERMOCOUPLE PILOT SHIELD 55345 VALVE PILOT ASSEMBLY COMPONENTS PAGE 38...

Страница 42: ...E DUE TO HIGH SURFACE TEMPERATURES KEEP CHILDREN CLOTHING AND FURNITURE AWAY This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and...

Страница 43: ...nformation on the front cover and on the previous page of this installa tion manual If you don t smell gas go to the next step B Locate pilot follow metal tube from gas control The pilot is located in...

Страница 44: ...p off wall switch or adjust setting on the thermostat or remote control NOTE The pilot will stay lit H Turn the pilot off by pushing in and turning the gas control knob to the OFF position DO NOT FORC...

Страница 45: ...switch to OFF 7 Disconnect manometer hose and tighten screw clockwise Screw should be snug do not over tighten 8 Attach manometer to manifold pressure tap to verify that it is completely sealed Manome...

Страница 46: ...DE THERMOPILE PILOT PAGE 43 PIEZO MOTOR GAS CONTROL KNOB INLET PRESSURE TAP OUTLET PRESSURE TAP LED FUEL CONVERSION PLUG ANTENNA PILOT ADJUSTMENT SCREW THERMOPILE MOTOR COVER WHITE DOTS FAN TERMINALS...

Страница 47: ...TO HIGH SURFACE TEMPERATURES KEEP CHILDREN CLOTHING AND FURNITURE AWAY This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and venti...

Страница 48: ...wo or three pushes on the piezo igni tor Hold the knob for about one 1 minute after the pilot is lit Release knob and it will pop back out Pilot should remain lit If it goes out repeat steps A C D Pus...

Страница 49: ...ceiver valve will be at the highest setting LOCAL SETTING Turn control knob clockwise to the PILOT position REMOTE SETTING The TR8220A transmitter can shut off the main burner and fan However the cont...

Страница 50: ...ach manometer to pressure tap using a 1 4 I D hose 4 Turn gas control knob to ON Note manometer reading 5 Disconnect manometer hose and tighten screw clockwise Screw should be snug do not over tighten...

Страница 51: ...not receive a signal within 6 hours from the transmitter The negative leads white must be connected to the terminals marked with white dots LED TROUBLESHOOTING In normal operation LED blinks once eve...

Страница 52: ...transmitter in a heated living space to make sure the main burner is not on continuously ON Mode With the control in the ON mode the flame and fan levels and the delay timer are changed with the UP an...

Страница 53: ...lack tips Open venturi setting slightly Open too far Blue flames Close venturi setting slightly NOTE IF SOOT IS PRESENT CHECK LOG POSITIONING BEFORE ADJUSTING BURNER VENTURI LOGS MUST NOT BLOCK BURNER...

Страница 54: ...ication is necessary remove restrictor by pulling it down and out of 5 exhaust pipe 5 Reinstall baffle by resting baffle front above flange along inside top of firebox opening Tip baffle back against...

Страница 55: ...ted at the inside top of the firebox and can be viewed through the glass The damper control is located under the firebox To reduce the amount of heat entering the room raise the damper control up and...

Страница 56: ...BY A QUALIFIED SERVICE PERSON THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND ANNUALLY BY A QUALIFIED SERVICE PERSON MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING BEDDIN...

Страница 57: ...TRUCTIONS A Check that pilot flame impinges on thermocouple Clean and or adjust pilot for maximum flame impingement B Ensure the thermocouple connection at gas valve is fully inserted and tight hand t...

Страница 58: ...aulty or connections are bad TROUBLESHOOTING 55345 only BURNER WILL NOT LIGHT FREQUENT PILOT OUTAGES A Pilot shield not installed B Pilot flame too high or too low causing pilot safety to drop out Cle...

Страница 59: ...n horizontal vent 1 4 6 mm rise per foot is required on horizontal venting E Inner vent pipe leaking exhaust gases back into firebox Check for leaks Repair if necessary F Improper vent cap installatio...

Страница 60: ...trol the main burner and fan Does transmitter change levels of flame height fan speed and set temperature Set levels of flame height and fan to 0 to shut off main burner and fan If the manual switch i...

Страница 61: ...n tank Check LP propane tank Refill if necessary PILOT WILL NOT STAY LIT AFTER CAREFULLY FOLLOWING LIGHTING INSTRUCTIONS A Check that pilot flame impinges on thermopiles Clean and or adjust pilot for...

Страница 62: ...s PILOT AND BURNER EXTINGUISH WHILE IN OPERATION C Improper pitch on horizontal vent 1 4 6 mm rise per foot is required on horizontal venting D Inner vent pipe leaking exhaust gases back into firebox...

Страница 63: ...t com REPLACEMENT PARTS LIST PAGE 60 GRILL REPLACEMENT TRF 200 Upper Hood TRF 201 Lower Grill TRF 200L Upper Hood Louver REFRACTORY PANELS Sandstone MTK G900 3 pc Refractory Panel Set MTK 901 Bottom R...

Страница 64: ......

Страница 65: ...PAGE 61...

Страница 66: ......

Страница 67: ...PAGE 62...

Отзывы: