Installation
Connecting mains cable
1.
De-energise the inverter.
2.
Switch off DC switch on the inverter.
3.
Secure it against reactivation.
4.
Correctly lay the mains cable from the power distrib-
utor to the inverter.
PE
PE
max. 28 mm
18 mm
16 mm
Fig. 21: Connect mains cable to the inverter
1
AC terminal
2
Mains cable
3
Sealing ring
4
Union nut
5.
Insert mains cable into the inverter and seal with
sealing ring and union nut. Tighten union nut to the
prescribed torque. Torques: 13 Nm (M40).
6.
If screw connections are not being used, leave the
blind plug in the screw connections.
IMPORTANT
INFORMATION
See the "Technical Data" chapter
for the dimensioning of the re-
quired AC line circuit breaker and
the cable cross-section and cable
type to be used. Ch. 9.1
If using an AC cable with an outer
diameter of 15-23 mm, the reducing
ring provided should be used.
Both single-wire (type NYY-J) and
multi-wire (type NYM-J) cables
without core end sleeves can be
used with the AC terminal.
When using cables with fine wires
(type H05../H07RN-F), core end
sleeves should be used. Ensure
that there is a contact surface of
18 mm.
IMPORTANT
INFORMATION
Existing cables and their routing
within the inverter must not be
changed. This can otherwise result
in malfunctions in the inverter.
2
3
4
6
7
8
9
10
11
1
5