© 2017 KOSTAL Solar Electric GmbH
Installation
3.4 Electrical connection
Inverter connections
1
DC connections
2
AC terminal
External connections
3
Line circuit breaker for inverter
4
Electricity meter
5
Public grid
IMPORTANT
INFORMATION
It must be ensured that the phases
of the AC terminal and the consum-
ers are assigned uniformly.
IMPORTANT
INFORMATION
This product may generate a direct
current in the outer protective
earthing conductor. If protective
residual current devices (RCD) or
residual current monitoring de-
vices (RCM) are used, only type B
≥300 mA RCDs or RCMs are per-
mitted on the AC side. Refer to the
manufacturer's declaration on our
website for exceptions.
Fig. 20: Overview of electrical connections