Kollmorgen
4/13/2012
Connector Pinout And Discriptions
S200 Position Node Installation Guide
27
7.0 CONNECTOR PINOUT AND DISCRIPTIONS
The following section describes the user connections to the S200 Position Node by connector. The front part of
this section presents AC / DC input Power and Power Terminal wirings for various drive models. J1 and TB1 vary
according to the model. Please refer to the proper description for your model.
7.1 PE A
LL
D
RIVE
M
ODELS
Each S200 Position Node product has at least one screw terminal from its frame exposed to the front of the
product for customer wiring to Protective Earth (PE) ground. This connection should be made with heavy gage,
high strand count wire and a ring lug terminal directly back to the incoming earth ground distribution block. Power
should not be applied if this connection does not exist.
PE Ground Terminals
(TYPICAL)