Data type
Value range
Binary
0 (off) / 1 (on)
1-byte unsigned int
0 ... 255
1-byte signed int
-128 ... 127
Percentage
0% ... 100%
2-byte unsigned int
0 ... 65535
2-byte signed int
-32768 ... 32767
2-byte float
-671088.64 ... 670760.96
3-byte RGB color
#000000 ... #ffffff
Each scene actuator can participate in up to 8 different scenes, identified through the
Scene #X
number
parameters.
For each scene in which the actuator is participating, an initial value for the actuator in that
scene can be defined (
Scene #X initial value
). This is the value that will be sent to the scene
actuator’s communication object when the specified scene number is recalled.
Finally, the
Scene #X allow saving
parameter determines whether this value should be updated
when a “store request” is received for the specified scene number. See
on
page 42 for additional information regarding storing of scenes.
3.7
Scenes
96