P-I control
Parameter name
Values
Output type
Continuous (1 byte)
/ PWM (1 bit)
Cycle time
1 ...
15
... 255 (x 1 min)
Control parameters
Custom parameters
Warm water heating (5K/150min)
Floor heating (5K/240min)
Electric heating (4K/100min)
Convection heating (4K/90min)
Proportional band
(Only if “custom parameters” is selected)
1 ...
4
... 15 (K)
Integral time
(Only if “custom parameters” is selected)
5 ...
150
... 255 (x 1 min)
Resending period
0
... 255 (x 1 min, 0 = Disabled)
If the proportional-integral (P-I) control method is selected, control commands will be sent
through the
Output variable (heating)
communication object. This will be a 1-bit object or a
1-byte object, depending on the setting of the
Output type
parameter.
For proper operation of the P-I control method, the
Cycle time
,
Proportional band
, and
Integral
time
parameters need to be defined. The latter two can be defined explicitly, or (more conve-
niently) one of the available predefined options may be selected from the
Control parameters
list.
See
on page 34 for a detailed description of all control parameters
involved.
Additional heating
Parameter name
Values
Additional heating
No
/ Yes
Additional heating band
(Only if additional heating is enabled)
-100 ...
-25
... -5 (x 0.1ºC)
Resending period
(Only if additional heating is enabled)
0
... 255 (x 1 min, 0 = Disabled)
These parameters enable control of auxiliary heating systems. For more information, please
refer to
2.4.6 Additional heating and cooling
on page 39.
3.5
Thermostats