Operation Logical Flowchart
Temperature
set point
Room air
temp.
Enabled?
YES
NO
Temperature
< set point?
Response
> 33%?
YES
NO
NO
NO
NO
Temperature
> set point?
YES
NO
Humidity
> set point?
NO
Determine propor-
tional response
Heater 1 ON
Heater 2 OFF
Response
> 66%?
Heater 1 OFF
Heater 2 ON
Response
> 99%?
Heater 1 ON
Heater 2 ON
Output proportional
heating signal
Run blower
YES
YES
YES
Humidity
set point
Room air
humidity
Humidity
< set point?
YES
YES
NO
Enable
humidifier
Determine propor-
tional response
Add humidity
Response
> 99%?
NO
Determine propor-
tional response
Run Compressor
(if any)
Run Remote HX
(if any)
Output proportional
cooling signal
YES
Determine propor-
tional response
Output proportional
cooling signal
Response
> 50%?
Run Compressor
(if any)
Enable DH
Run Remote HX
(if any)
YES
General Flowchart
Specific units may vary.
NO
OPERA