Remote Condensers and Heat Exchangers
Select branch-circuit voltage from the condenser nameplate data.
Select branch-circuit conductors from the condenser nameplate
data.
Connect the conductors as shown. Note that L3 will not be pres-
ent on single-phase condensers.
Single-phase motors inherently turn the correct direction. A three-
phase branch circuit must be tested for proper motor rotation.
1. Temporarily connect a jumper across the enable contacts as
shown.
2. Apply electric power to the branch circuit connected to
terminals L1, L2, and L3.
3. If the fans do not blow air in the proper direction (see below)
a) disconnect electric power, following all safety precautions
b) a qualified person should interchange any two branch
circuit conductors.
DO NOT CHANGE ANY FACTORY WIRES.
c) return to step 2.
4. If the fans blow air in the proper direction (see below) then
a) disconnect electric power
b) remove the temporary jumper.
L1
L2 L3
(if any)
L1 L2 L3
Enable
temporary
jumper
Proper air-flow direction for vertical-flow
Proper air-flow direction for horizontal-flow