![Klimaire Ecosaire CM Series Скачать руководство пользователя страница 52](http://html1.mh-extra.com/html/klimaire/ecosaire-cm-series/ecosaire-cm-series_installation-operation-and-maintenance-manual_1977768052.webp)
Ecos
aire
®
CM Series Precision Air Conditioner Owners Manual
52
Ecos
aire
®
July 2007
Data subject to change without notice.
Startup Adjust Remote Heat Exchanger Controls
HEAT EXCHANGER FAN THERMOSTATS
Remote heat exchangers have a minimum number of fans that run whenever the
Ecos
aire
® unit is in cooling
mode. Other fans may be controlled by thermostats sensing outdoor air temperature. Where this is the case,
the thermostats must be adjusted at installation, using the diagrams below.
HEAT EXCHANGER FAN ROTATION
The remote heat exchanger fans must rotate so as to pro-
duce an upward air discharge as shown.
Single-phase fans will inherently turn the proper direc-
tion. If three-phase fans turn the wrong way, a qualified
person should disconnect the branch circuit and inter-
change any two wires on the power inlet lugs in the con-
denser control enclosure.
Do not move any factory-
installed wires.
Discharge air must flow upward.
optional remote condenser
xx
xx
xx
xx
xx
xx
75
No adjustments necessary.
-30
-30
75
80
75
fan contactors
set point (°F)
fan thermostat
HEAT EXCHANGER
CONTROL ENCLOSURE
FAN ARRANGEMENT
Air-Cooled Direct Expansion, Glycol-Cooled Direct Expansion,
Air-Cooled DualCool, & Glycol-Cooled DualCool Units Only
ST
ARTUP
SAMPLE
Number and location of
component
s may vary
.