Ecos
aire
®
CM Series Precision Air Conditioner Owners Manual
Installation Piping Refrigerant
26
Ecos
aire
®
July 2007
Data subject to change without notice.
air-cooled Direct Expansion and DualCool units only
When shipped, remote air-cooled units contain a refrigerant holding charge.
The holding charge must be
reclaimed before removing the caps on the remote-condenser tube stubs. Failure to reclaim the holding
charge can lead to property damage and/or personal injury.
Open the compressor rotalock valves and reclaim the holding charge.
NOTE: After the following step, installation must proceed immediately and rapidly, since the filter-
drier will be exposed to atmosphere.
Close the rotalock valves and remove the reclaim equipment. Remove the condenser tube-stub caps with
a tube cutter. To prevent the introduction of foreign materials into the refrigeration system, do not use a
hack saw.
reclaim manifold
(by others)
Open the compressor rotalock
valves for reclaiming.
Refrigerant tubes are
capped when shipped.
Open the access panels near the refrigerant tube stubs. Locate the hot-gas tube stub.
Locate the Schraeder-type access valve on the hot-gas tube inside the cabinet.
The position shown is not typical.
Attach a reclaim hose to the Schraeder valve.
INST
ALLA
TION
SAMPLE
Number
, location, and
appearnce of component
s
may vary
.