Air-Cooled Direct-Expansion and Air-Cooled DualCool Units Only
Water-Cooled Direct-Expansion, Water-Cooled DualCool, and FreeCool Units Only
Owners Manual Ecos
aire
®
CM Series Precision Air Conditioner
Ecos
aire
®
July 2007 31
Data subject to change without notice.
Piping
Installation
Water-Cooled Direct-Expansion, Water-Cooled DualCool, and FreeCool
Units are shipped with refrigerant. Note the amount from the unit name-
plate.
Some applications may require that the relief-valve outlet be
routed outdoors. In this case:
Locate the refrigerant receiver inside the air-handler unit. The relief
valve is on top of the receiver.
Attach a suitably-sized tube to the relief-valve outlet, taking care not to
damage the relief valve. Use mechanical connectors only, do not sweat
or braze.
Route the tube through a cabinet knockout near the water or
glycol tubes, and to a suitable point of release.
Release the liquid-line solenoid valve from the locked-open
position by turning the manual stem counter-clockwise all the
way.
Replace and tighten the stem cap.