Owners Manual Ecos
aire
®
CM Series Precision Air Conditioner
Ecos
aire
®
July 2007 55
Data subject to change without notice.
For glycol coolers, be sure that the system is full of glycol solution.
Turn off electrical power to the remote heat exchanger.
Carefully attach a temporary jumper to the enable input of the remote
heat exchanger, as shown.
Close the electrical enclosure of the remote heat exchanger.
Turn on the electrical power to the remote heat exchanger.
Confirm that the fans (and pumps, if any) of the remote heat exchanger
operate.
For remote heat exchangers with three-phase fans, confirm that the
fans turn in the proper direction to blow air upward. If they do not, a
qualified person should disconnect power from the remote heat
exchanger, swap any two branch-circuit wires, and re-connect electrical
power to the remote heat exchanger.
Do not move any factory-
installed wires.
For Air-Cooled Direct Expansion and Air-Cooled DualCool units,
remove the temporary jumper installed in step above. For all others,
leave jumper in place and go to next page.
Adjust Remote Heat Exchanger Controls
Startup
Air-Cooled Direct Expansion, Glycol-Cooled Direct Expansion,
Air-Cooled DualCool, & Glycol-Cooled DualCool Units Only
xx
xx
SAMPLE
Number and location of
component
s may vary
.
ST
ARTUP