Ecos
aire
®
CM Series Precision Air Conditioner Owners Manual
56
Ecos
aire
®
July 2007
Data subject to change without notice.
REQUIRED GLYCOL FLOWS (GPM)
Outdoor
Temp. 95°F
Outdoor
Temp. 100°F
Glycol-Cooled
Direct
Expansion
or
Glycol-Cooled
DualCool
or
FreeCool
Outdoor
Temp. 105°F
Model No. CM010 CM015 CM020 CM030 CM050 CM070 CM080 CM100
6.5
5.0
8.7
9.5
17.7
37.2
42.0
24.6
18.9
GPM
lpm
GPM
lpm
GPM
lpm
GPM
lpm
32.9
36
67.0
141
159
6.5
5.0
8.7
9.5
17.7
37.2
42.0
24.6
18.9
32.9
36
67.0
141
159
6.5
5.0
8.7
9.5
17.7
37.2
42.0
24.6
18.9
32.9
36
67.0
141
159
Outdoor
Temp. 110°F
13.0
10.1
17.4
21.9
41.5
74.4
84.0
49.2
38.2
65.9
82.9
157
26.5
100
26.5
100
26.5
100
50.9
193
282
318
Startup Check Remote Heat Exchanger Operation
Glycol-Cooled Direct Expansion, Glycol-Cooled DualCool,
& FreeCool Units Only
(continued from previous page)
Check that the glycol solution is flowing at the proper flow rate. See table below.
After the pump(s) run for a while, residual air may be removed. Check that the system is still full of glycol
solution.
Turn off the electrical power to the remote heat exchanger.
Remove the jumper from step 2 (previous page).
ST