CM Series Precision Air Conditioner              Owners Manual

60

Ecos

aire

®

July   2007

Data subject to change without notice.

Humidifier (if any)

Some units may be equipped

with electrode-type humidifiers.
Access the humidifier as shown in
the diagram below.

IMPORTANT!

The electrode plugs

on top of

the cylinder must be pressed firmly
onto the electrode pins.  If a plug is
loose, temporarily disconnect elec-
tric power and squeeze the plug
with pliers.  

Loose plugs will

cause overheating and prossible
melting of the plugs.

Components burnt due to loose
connections are not covered under
warranty.

Open the field-installed shut-off

valve on the water inlet line.  Push
the AUTO/ON/OFF/DRAIN switch
to “ON.” 

The humidifier light will come on.

The humidifier contactor and the fill
solenoid valve will energize, slowly
filling the cylinder with water.  The
water level will rise until the current
draw through the electrodes reach-
es the pre-set value determined by
the capacity control setting.
Normally, this is before the water
reaches the top.

While the cylinder is filling, locate

the three power leads on the top of
the cylinder and check that the line
voltage is present at all leads.

IMPORTANT!

Low conductivity water will

cause the water level to rise to
the top of the cylinder activating
the High Water Level alarm light.
This is NOT a concern.  The
cylinder will continue to heat,
boil and refill in short cycles
until the mineral concentration
within the cylinder increases to
normal.  As it does, the water
level will also drop to normal.

The water cylinder will begin to

boil shortly after it stops filling.  As
the water boils away, the water
level in the cylinder will drop.
When it has dropped a preset
amount, the fill valve will open to
refill the cylinder.  Optimum con-
ductivity is automatically main-
tained with short drain cycles only
when necessary.

Check the current on all power

lines to the cylinder.  The current
will vary with water level.  The max-
imum current will be reached just
as the fill valve closes and should
agree with the nominal amps listed
below.

Should normalization of the unit

be required immediately after start-
up, the installer may speed up the
process by artificially increasing
water conductivity.  During a fill
cycle, the installer should dissolve
half a teaspoon of table salt

(NO

MORE)

in a cup of water and add it

to the cylinder by means of the fill
cup attached to the plumbing sec-
tion.

Open the plumbing compartment

and add salt solution through the
cylinder outlet.  Excessive amounts
of salt will result in erratic operation
of the unit; however, normalization
of the unit will occur automatically
through the solid-state control
sequence.

Startup                                                                                    Humidifier   

Humidifier Amp Draw

Unit Voltage
Humidifier Nominal Amps

200 v

18.5

230 v

16.1

460 v

8.0

Humidifier

ST
ARTUP

SAMPLE

Number and location of

component

s may vary

.

Содержание Ecosaire CM Series

Страница 1: ...klimaireINTL klimaireINTL com 1 647 477 3333 1 646 808 0240 KLIMAIRE International www klimaireINTL com Ceiling Mount Precision Cooling Systems Installation Operation Maintenance Manual...

Страница 2: ...saire system Please read the entire manual carefully and if you have any questions con tact your local Ecosaire representative Your warranty is valid only if conditions explained in this manual are me...

Страница 3: ...ty 75 Operation Contents 77 Maintenance Schedule 78 Maintenance Record 80 Maintenance Tasks 83 Logical Flow Charts 90 Supervisaire Controller 91 Password 92 Enable Disable 93 Clock 94 Set Point Adjust...

Страница 4: ...network together with a supervisory panel complete with a backlit graph ics display for robust redundant environment control At the same time the network can be connected to a personal computer super...

Страница 5: ...e units They may be easily replaced from the filter access door Refrigeration circuit is fitted with filter drier sight glass mois ture indicator liquid line solenoid valve adjustable externally equal...

Страница 6: ...cooled condensers are available for the following conditions Design Standard Ambient Low Ambient Temp min max min max 95 F 35 C 0 105 F 17 41 C 40 105 F 40 41 C 100 F 38 C 0 110 F 17 43 C 40 110 F 40...

Страница 7: ...control room conditions Heat is transferred via pumped glycol fluid flow to an outdoor heat exchanger The outdoor heat exchanger has multiple direct drive propeller fans and is built with aluminum bod...

Страница 8: ...When the outdoor temperature is below 60 F 16 C the Ecosaire unit operates its refrigeration system to move heat into a flow of glycol Refrigeration condensing pressure is controlled by pressure con...

Страница 9: ...r temperature of the chilled water becomes inade quate for proper operation the unit will automatically change to Air Cooled Direct Expansion Air cooled condensers are available for the following cond...

Страница 10: ...gs The unit is rated for use with 45 F 7 2 C chilled water For flow rates and other details see Installation Piping If the flow rate or temperature of the chilled water becomes inadequate for proper o...

Страница 11: ...s rated for use with 45 F 7 2 C chilled water For flow rates and other details see Installation Piping If the flow rate or temperature of the chilled water becomes inadequate for proper operation the...

Страница 12: ...e July 2007 Data subject to change without notice Product Description Air Flow Options DESCRIPTION Horizontal Straight Horizontal Left Horizontal Down Horizontal Right S A M P L E N u m b e r l o c a...

Страница 13: ...noid Valve D1 D2 D3 O 2 way Water Reg Valve D2 D3 F G W P 3 way Water Reg Valve D2 D3 F G W Q 2 way Water Modul Valve C D2 D3 F G W R 3 way Water Modul Valve C D2 D3 F G W S Water Flow Switch T Non fu...

Страница 14: ...ONTROL AIR CONDITIONER Before calling for assistance be sure to have the model serial and tag numbers available for the service department Be sure the voltage and current ratings of the unit branch ci...

Страница 15: ...m air to escape into the ceiling plenum Because of the small number of per sonnel in a typical computer site out door air should be reduced to less than 5 of the total circulated air If outdoor air is...

Страница 16: ...ng plastering etc are underway it must be covered with the shipping carton or plastic film in order to keep the filters and internal components clean Do not allow water plaster con crete dusts or othe...

Страница 17: ...Insulate hot gas tubes where they might be accidentally touched Lifting holes are provided at the top of the support legs The nuts and bolts securing the unit to the crate are used to mount the lower...

Страница 18: ...Areas subject to heavy snow and ice accumulation should be avoided Areas subject to public access should be avoid ed Locate outdoor units in an area of clean air away from steam hot air or fume exhau...

Страница 19: ...es result in higher power requirements and increased noise The maxi mum external static pressure is specified for each unit Static pressures higher than specified may reduce air flow below the mini mu...

Страница 20: ...ECOSaire There should be no elbows transitions offsets duct heaters or other flow interruptions closer that 5 X the width of the blower On special order Dectron may be able to provide bottom top or s...

Страница 21: ...of the window RIGHT Vanes and straight length allow air to flow evenly RIGHT Vanes and straight length allow air to flow evenly RIGHT Air can follow this transition RIGHT Sufficient straight length al...

Страница 22: ...four feet of the Ecosaire unit Reduce to 1 4 O D and connect to the 1 4 compression fitting on the supply port as shown IMPORTANT Be sure the shut off valve is closed after the connections are comple...

Страница 23: ...ut let side of the P trap may be neces sary Follow standard procedures Route drain pipe Route the drain pipe so that the only trap is the P trap In horizontal runs slope the pipe downward at least 1 4...

Страница 24: ...subject to change without notice If pressure testing be sure to isolate the compressor from high pressure To System To System S a m p l e C o m p o n e n t s a n d t h e i r l o c a t i o n s m a y v...

Страница 25: ...ocate the refrigerant liquid line solenoid valves Some units may be equipped with manual lift valves Where this is the case 1 Using two wrenches remove the manual stem covers 2 Turn the manual stems c...

Страница 26: ...proceed immediately and rapidly since the filter drier will be exposed to atmosphere Close the rotalock valves and remove the reclaim equipment Remove the condenser tube stub caps with a tube cutter...

Страница 27: ...8 7 8 1 1 8 1 1 8 1 1 8 1 1 8 1 1 8 1 3 8 1 3 8 5 8 5 8 5 8 5 8 5 8 3 4 3 4 3 4 5 8 5 8 5 8 5 8 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 7 8 7 8 Air Cooled Direct Expansion and Air Cooled DualCool Uni...

Страница 28: ...e valves and other com ponents If the inside of the tubes is contami nated with dirt oil sludge rust or other materials then they must be thoroughly cleaned IMPORTANT Never allow liquid water to enter...

Страница 29: ...M headmaster Ecosaire Unit with without HGBV HGBV Model lb lb CM010 1 5 1 0 ______ CM015 1 5 1 0 ______ CM020 3 0 2 0 ______ CM030 4 5 3 0 ______ CM050 6 5 4 5 ______ CM070 7 5 5 0 ______ CM080 15 0 1...

Страница 30: ...service gauges an electronic micron level vacuum gauge and a vacuum pump as shown below Use core removal adapters to remove the cores from Schraeder type access valves To insure a correct vacuum read...

Страница 31: ...tlet be routed outdoors In this case Locate the refrigerant receiver inside the air handler unit The relief valve is on top of the receiver Attach a suitably sized tube to the relief valve outlet taki...

Страница 32: ...whenever the Ecosaire unit is operational Do not allow a timer or other device to inhibit operation at any time the Ecosaire unit is operational IMPORTANT Cooling water must be protected from freezin...

Страница 33: ...factory piping dia grams Install a fill port at the highest point of the sys tem To insure proper gly col water ratio never use automatic fillers Where copper tubing use Type L only is used joints sh...

Страница 34: ...pen the fill valve and all air vents including the petcocks at the top of the FreeCool coils on the right hand side of the unit The pipe plugs on the pump impeller housing and at the top of the room u...

Страница 35: ...same size as the chilled water valve for both the inlet and out let A shut off valve by others should be installed on the the inlet and outlet line Insulate the chilled water lines where they run thro...

Страница 36: ...direction Use properly sized wire Refer to the unit nameplate for electrical ratings Size wires according to applicable codes with allowance for voltage drops Unit terminal voltage should be nominal...

Страница 37: ...rily connect a jumper across the enable contacts as shown 2 Apply electric power to the branch circuit connected to terminals L1 L2 and L3 3 If the fans do not blow air in the proper direction see bel...

Страница 38: ...0m 3 gang wall box by others At each end of the cable loop the modular telephone cable once as shown through clamp on split ferrite EMI cores by others The cores should have an impedance near 240 at 1...

Страница 39: ...W BLUE WHITE BLACK RED GREEN YELLOW BLUE WHITE BLACK RED GREEN YELLOW BLUE WHITE BLACK RED GREEN YELLOW BLUE Assembling data reversed modular telephone cable Note that the lock tabs of the plugs are o...

Страница 40: ...modular telephone plug by others is to be inserted into the display jack Insert 6P6C modular tele phone plug by others into the modular port Unit Controller Modular cable to round cable adapter by oth...

Страница 41: ...See previous page for cable details Allow at least 10 inches of free cable for connection to the display The six pin modular telephone plug by others is to be inserted into the display jack Unit Cont...

Страница 42: ...the end of the cable thorugh the hole in the sub base as shown Using care to maintain level screw the sub base to the wall box here Connect the cable to the modular telephone jack on the back of the d...

Страница 43: ...an internal Ecosaire power source The condenser control wire size must be selected to allow for contactor coil inrush currents See the chart at right Alternatively a pilot relay by others may be inst...

Страница 44: ...es provid ed by others In this case the remote on off switch must be wired to the Ecosaire controls see unit field wiring diagram in unit information package When dry contacts are open the unit will b...

Страница 45: ...s Startup Page Supervisaire Controller Interface 46 Pre Startup Adjustments 49 Airflow 51 Remote Heat Exchanger 52 Humidifier 60 Add Refrigerant 61 Expansion Valve 62 Pre Startup Checklist 63 Enable O...

Страница 46: ...ns and menus The button is used for scrolling upward to change set points enter passwords and to select display screens and menus The button is used to navi gate through menu selections and to accept...

Страница 47: ...ight appears briefly followed by the unit default screen Optional remote displays may show the message NO LINK Where this is the case the address of the display must be set To set the display address...

Страница 48: ...shown On initial application of power the panel will appear as shown Wait while the controller checks its internal functions self test please wait Dectron ECOS SuperVisaire Version x x mm dd yy Room S...

Страница 49: ...rn to the default Room Status screen Alternatively press Esc as neces sary to return to the default screen To access the System ON OFF menu press Prg and enter the password as discussed in Startup Pre...

Страница 50: ...d when prompted press to move the cursor to the password Press until the password reads 0008 If you overshoot press Press The password is entered and changes can be made Enter Password 0000 Enter Pass...

Страница 51: ...ld be within 10 of the value stated on the submittal forms Some Ecosaire units may have voltage monitors that prevent operation in the event the branch circuit voltage is too high too low has lost a p...

Страница 52: ...as to pro duce an upward air discharge as shown Single phase fans will inherently turn the proper direc tion If three phase fans turn the wrong way a qualified person should disconnect the branch cir...

Страница 53: ...emote heat exchanger fans must rotate so as to pro duce an upward air discharge as shown Single phase fans will inherently turn the proper direc tion If three phase fans turn the wrong way a qualified...

Страница 54: ...ntrol valve as shown at right Open the plug on the end of the valve by turning it counter clockwise Save the plug for future use Keep the O ring clean Locate the hex broached adjusting screw inside th...

Страница 55: ...hangers with three phase fans confirm that the fans turn in the proper direction to blow air upward If they do not a qualified person should disconnect power from the remote heat exchanger swap any tw...

Страница 56: ...32 9 36 67 0 141 159 6 5 5 0 8 7 9 5 17 7 37 2 42 0 24 6 18 9 32 9 36 67 0 141 159 Outdoor Temp 110 F 13 0 10 1 17 4 21 9 41 5 74 4 84 0 49 2 38 2 65 9 82 9 157 26 5 100 26 5 100 26 5 100 50 9 193 282...

Страница 57: ...ly For all units be sure the compressor rotalock valves are open Locate the refrigerant receiver in the remote condenser Be sure the rotalock valves on the receiver are open by turning the stems count...

Страница 58: ...ithout notice Locate the refrigerant receiver in the unit Be sure the rotalock valves on the receiver are open by turning the stems counter clockwise Replace the stem caps Glycol Cooled Direct Expansi...

Страница 59: ...07 59 Data subject to change without notice For Glycol Cooled DualCool FreeCool or Chilled Water units be sure that any fluid valves by others are open For Water Cooled Direct Expansion units be sure...

Страница 60: ...cylinder will continue to heat boil and refill in short cycles until the mineral concentration within the cylinder increases to normal As it does the water level will also drop to normal The water cy...

Страница 61: ...e unit through the suction access valve while the compressor is running NEVER ADD LIQUID REFRIGERANT TO THE SUCTION ACCESS VALVE Units with two refrigeration circuits will have two sight glasses and t...

Страница 62: ...r Tape the insulation to prevent air flow from changing the temperature reading Locate and identify the refrigerant sight glass Locate and identify the expansion valve Suction Tube Startup Prepare to...

Страница 63: ...ate drain P trap has been filled with water and that the drain works For units with humidifiers con firm that the water supply tube is complete and tested For units requiring a conden sate pump confir...

Страница 64: ...fusers are unobstructed Confirm that all construction dust and debris has been removed from ducts and plenums For glycol cooled and Free Cool units make sure all pipe air vents are closed tightly Rem...

Страница 65: ...tedly until the cursor is at the desired value The example is to change the hour Press either or to change the selected value To store the setting press until the cursor is back in the upper left corn...

Страница 66: ...lay 015 sec Humidity Alarms High XX X RH Low 20 0 RH Delay 015 sec Humidity Alarms High XX X RH Low 20 0 RH Delay 015 sec Startup Pre Startup Adjustments Humidity Set Points Press repeatedly to access...

Страница 67: ...perature set pts Set point xx x F Temperature set pts Set point xx x F To access the temperature alarm set point screen press twice Temperature Alarms High 80 0 F Low 60 0 F Delay 015 sec Press Prg en...

Страница 68: ...nums 1 Apply electric power Allow at least 10 hours of crankcase heater operation before enabling a compressor 2 Do not allow a compressor to run without adequate refrigerant Press to move the cursor...

Страница 69: ...adjusting screw counter clockwise to lower the head pressure or clockwise to raise the head pressure as needed to make the head pressure at teh compressor be 250PSI 15 PSI Return the plug to the valve...

Страница 70: ...pressure should be above 50 PSI If it is not above 50 PSI stop and determine the cause The discharge pressure should be 250 PSI 15 PSI If it is not then check that the coling fluid temperature and flo...

Страница 71: ...5 40 4 4 71 5 42 5 5 74 5 44 6 6 77 6 46 7 8 80 8 48 8 9 84 0 50 10 87 4 52 11 1 90 8 54 12 2 94 3 56 13 3 97 9 58 14 4 101 6 60 15 5 105 4 62 16 6 109 3 64 17 8 113 2 66 18 9 117 3 68 20 121 4 70 21...

Страница 72: ...s Temperatures Coil 1 aa a F Coil 2 bb b F To access a customer temperature if any aa a press Temperatures Customer aa a F Valve Position bbb To access UNIT STATUS press aaa is the blower status bbb i...

Страница 73: ...true Date and time set All alarms cleared ECOSaire Startup Report Warranty Registration Warranty void unless this form is completed and a copy returned to factory within 2 weeks after start up Instal...

Страница 74: ...nty void unless this form is completed and a copy returned to factory within 2 weeks after start up Operational Data NOTE To obtain adequate readings a delay of ten 10 minutes is required after every...

Страница 75: ...r 9 Seller warrants that the title conveyed under the terms of this Contract shall be good and marketable and that the goods shall be delivered free from any lien encumbrance or security interest what...

Страница 76: ...a common carrier licensed public trucker or Buyer or its agent viii any loss or damage caused by failure to install or maintain equipment in accordance with Seller s instructions including without lim...

Страница 77: ...nts Operation OPERATION Page Maintenance Schedule 78 Maintenance Record 80 Maintenance Tasks 83 Logical Flow Charts 90 Supervisaire Controller Interface 91 Password 92 Enable Disable 93 Clock 94 Set P...

Страница 78: ...or so tight as to cause excessive shaft bearing wear See Operation Maintenance Blower Check that the condensate drain pan s is clean For units so equipped check that the remote heat exchanger is clean...

Страница 79: ...tenance Record Maintenance Operation Ecosaire July 2007 79 Data subject to change without notice Photostat the next two pages as needed Tape the spine edges of the copies together Post the copies as a...

Страница 80: ...rature Room humidity Air filters clean Humidifier strainer clean Humidifier high water sensor not lit Blower belt wear OK Blower belt tension OK Condensate drain pan clean Remote heat exchanger clean...

Страница 81: ...Owners Manual Ecosaire CM Series Precision Air Conditioner Maintenance Record Maintenance Operation Ecosaire July 2007 81 Data subject to change without notice DATES...

Страница 82: ...Ecosaire CM Series Precision Air Conditioner Owners Manual 82 Ecosaire July 2007 Data subject to change without notice Operation Maintenance This page intentionally left blank OPERATION...

Страница 83: ...may vary Some units may have intakes for outdoor air CHECK THAT ALL FILTERS ARE CLEAN AND IN PLACE The size and number of filters may vary Air filters should be checked at least every month Dirty fil...

Страница 84: ...down with warm water spray and a mild non foaming detergent To protect the heat exchangers from corrosion do not use alkaline or acidic cleaning solution The condenser should not be enclosed within a...

Страница 85: ...es after five minutes of compressor operation If bubbles or droplets are noted contact a service technician or the factory Bubbles in the sight glass indicate problems such as a possible loss of refri...

Страница 86: ...haft centers Multiply the number of inches by 1 64 This will be the deflection D in the diagram at right ex For S 32 inches D 32in x 1 64 1 2 in Measure the diameter of the smaller sheave Read the V b...

Страница 87: ...20 0 21 2 24 8 8V 19 2 23 3 27 3 16 7 20 3 23 8 13 0 15 6 18 5 4 4 8 5 9 0 11 8 12 5 16 0 5VX 3 65 4 12 4 5 5 6 8 6 7 5 5 7 6 0 10 6 3V 5 5 6 4 7 5 4 8 5 7 6 6 3 9 4 4 5 0 2 2 3 35 3 65 4 12 4 5 5 6 8...

Страница 88: ...of the unit CAUTION Cylinder and any undrained water might still be HOT MANDATORY CLEANING OF THE DRAIN VALVE Always clean the drain valve before installing a new cylinder since the valve port may be...

Страница 89: ...be taken so that the cylinder leads of the same color are always directly opposite each other as indicated by the dot formation on the top of the cylinder 6 The white cylinder plug on all units is fo...

Страница 90: ...eater 1 OFF Heater 2 ON Response 99 Heater 1 ON Heater 2 ON Output proportional heating signal Run blower YES YES YES Humidity set point Room air humidity Humidity set point YES YES NO Enable humidifi...

Страница 91: ...to change set points enter passwords and to select display screens and menus The button is used to navi gate through menu selections and to accept changes The Prg button is used to access the set poin...

Страница 92: ...mpted press to move the cursor to the password Press until the password reads 0008 If you overshoot press Press The password is entered and changes can be made Enter Password 0000 Enter Password 0008...

Страница 93: ...o the default Room Status screen Alternatively press Esc as neces sary to return to the default screen To access the System ON OFF menu press Prg and enter the password as discussed in Startup Pre sta...

Страница 94: ...dly until the cursor is at the desired value The example is to change the hour Press either or to change the selected value To store the setting press until the cursor is back in the upper left corner...

Страница 95: ...ec Humidity Alarms High 80 0 RH Low 20 0 RH Delay 015 sec Humidity Alarms High XX X RH Low 20 0 RH Delay 015 sec Humidity Alarms High XX X RH Low 20 0 RH Delay 015 sec Press repeatedly to access Humid...

Страница 96: ...re set pts Set point xx x F Temperature set pts Set point xx x F To access the temperature alarm set point screen press twice Temperature Alarms High 80 0 F Low 60 0 F Delay 015 sec Press Prg enter th...

Страница 97: ...urrent alarms press repeatedly noting each alarm Eventually the screen will show No more alarms NO MORE ALARMS Press ENTER to clear Press ALARM to view To clear the current alarms press The alarms are...

Страница 98: ...STATUS after a short delay Select Configuration Menu 1 by pressing Prg and Esc at the same time Config Menu 1 System Run Hours Alarm History Control setup To select Alarm History press twice To view p...

Страница 99: ...view the run times for the BLOWER and the HEATERS press EQUIPMENT RUN HOURS Blower xxxxxhrs Heat 1 xxxxxhrs Heat 2 xxxxxhrs To view the run times for the HUMIDIFIER and the FreeCool VALVES if any pre...

Страница 100: ...flow of air and that the air is less than 105 F 4 For water cooled units check that water is flowing and of proper temperature 5 Check that all refrigerant isolation valves are open CORRECTIONS Consul...

Страница 101: ...ller Diagnostics Operation ALARM 00 00 00 00 Fire detected CHECKS 1 Check for fire or smoke 2 Check for fire alarm input voltage CORRECTIONS If fire or smoke is found follow proper emergency procedure...

Страница 102: ...after the compressor has been running for two minutes 6 Check the operation of the refrig erant low pressure switch It should open as the pressure falls below 20 PSI and close as the pressure rises ab...

Страница 103: ...dows new electrical equipment more people than usual etc CORRECTIONS If controller does not agree with known good thermometer contact factory for corrective measures If room temperature is too high or...

Страница 104: ...measures If the cable continuity is correct but the sensor resistance does not correspond to that shown in the chart for the known temperature the sensor must be replaced If controller does not agree...

Страница 105: ...ling band 1 Heating Band may too small 2 Integral term may be too small CORRECTIONS Correct as necessary If the heating capacity is not sufficient contact factory for solutions Close any doors or wind...

Страница 106: ...the load 2 Check for changes in humidity load since design stage CORRECTIONS If the humidifier capacity is not sufficient contact the factory for solutions Close any doors or windows that have been l...

Страница 107: ...ear with relative humidity This signal cannot be calibrated in the field Contact the factory for software solutions Volts DC Relative humidity Air and fluid tem peratures are measured by NTC thermisto...