KLP073008
3-11
3.2.11.2
DISPLAY MODEL
Enter
UTIL
menu and rotate either
VOLTAGE
or
CURRENT
control until status display reads
MODL
(see PAR. 3.2.11).
• The
DC VOLTS
display shows the model voltage rating (e.g, 75 for KLP 75-33-1200).
• The
DC AMPS
display shows the model current rating (e.g, 33 for KLP 75-33-1200).
3.2.11.3
RELAY CONTROL
Enter
UTIL
menu and rotate either
VOLTAGE
or
CURRENT
control until status display reads
RELY
(see PAR. 3.2.11). Press
DC OUTPUT
switch to enter Relay Control menu.
• The
DC VOLTS
display indicates whether the relay is currently ON (energized) or OFF
(deenergized).
• Rotate either
VOLTAGE
or
CURRENT
control to see the available relay control modes
in the status display. The list of modes in the order they appear are:
FLT
(factory default) - Relay is set to energize automatically upon detection of one of
three preselected conditions:
NORM
: (factory default) relay energizes immediately upon detection of a system
(fatal) error:
V->C
: relay energizes immediately upon detection of a system (fatal) error and,
after a user-programmable delay, the relay energizes upon a transition
from constant voltage (CV) to constant current (CC) mode.
C->V
: relay energizes immediately upon detection of a system (fatal) error and,
after a user-programmable delay, the relay energizes upon a transition
from constant current (CC) to constant voltage (CV) mode.
MAN -
Relay on/off is controlled manually, directly from the front panel (see below).
LIST
- Relay on/off is controlled remotely using LIST commands via GPIB or RS 232
interface (see PARs. B.10 and B.11).
1. To select mode rotate either
VOLTAGE
or
CURRENT
control until status display reads
FLT
(factory),
MAN
(manual), or
LIST
. Then press
DC OUTPUT
switch to save selection. Pro-
ceed to step 2 if
FLT
is selected, proceed to step 4 if
MAN
is selected, otherwise skip to step
5.
2. If
FLT
is selected, rotate
VOLTAGE
or
CURRENT
control to select
NORM
,
V->C
, or
C->V
. in
the status display. If
NORM
is selected, press the
DC OUTPUT
switch to save selection and
skip to step 5. If
V->C
, or
C->V
is selected, proceed to step 3.
3. While
V->C
or
C->V
is in the status display, the
DC AMPERES
display shows the delay in
seconds, from 000.5 to 128.0:
NNND
, where
NNN
is an integer from 0 to 128 and
D
will be
either .0 or .5 (000.0 is not permitted). The delay determines the length of time that the unit
must be operating in the new mode before energizing the relay.
The factory default delay time is set to 1.0 seconds to prevent false tripping of the relay dur-
ing application of output power to low impedance or highly reactive loads. If false tripping
occurs, this delay may be increased as needed.
To change the delay, press in and rotate either the
VOLTAGE
or
CURRENT
control; release
the control when the desired delay is showing in the
DC AMPERES
display. Press the
DC
OUTPUT
switch to save selection and skip to step 5.
Содержание KLP SERIES
Страница 2: ......
Страница 6: ......
Страница 14: ...viii KLP073008 FIGURE 1 1 KLP SERIES POWER SUPPLY...
Страница 20: ...1 6 KLP 073008 FIGURE 1 3 KLP SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING SHEET 1 OF 2 R DWG MECH 3010266...
Страница 21: ...KLP 073008 1 7 FIGURE 1 3 KLP SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING SHEET 2 OF 2...
Страница 26: ......
Страница 40: ......
Страница 86: ......