1-2
KLP 073008
FIGURE 1-2. KLP OPERATING REGIONS
TABLE 1-1. MODEL PARAMETERS
Model number
Rated
Voltage
Range
(1)
Maximum
current for
rated voltage
Minimum
programmable
current
Rated
Current
Range
(1)
Maximum
voltage for
rated current
Ripple and noise
Efficiency
@115 Va-c
rms
p-p
(2)
KLP 20-120-1200
(3)
0-20V
60A@20V
1.6A
0-120A
10V@120A
10 mV
75 mV
82%
KLP 36-60-1200
(3)
0-36V
33.3A@36V
0.8A
0-60A
20V@60A
10 mV
125 mV
83%
KLP 75-33-1200
0-75V
16A@75V
0.4A
0-33.3A
10 mV
125 mV
84%
KLP 150-16-1200
0-150V
8A@150V
0.2A
0-16A
75V@16A
10 mV
125 mV
86%
KLP 300-8-1200
0-300V
4A@300V
0.1A
0-8A
150V@8A
20 mV
300 mV
87%
KLP 600-4-1200
(3)
0-600V
2A@600V
0.05A
0-4A
300V@4A
tbd
tbd
88%
(1) The maximum current and voltage are constrained by the 1200 watt power limitation, see Figure 1-2.
(2) Bandwidth: 20MHz; low frequency ripple may be higher at loads less than 30 Watts..
(3) Not all models available at this time. Please contact factory for additional information.