3-10
KLP073008
• If analog control is used, only the master is configured for analog control (the slave is
controlled digitally by the master).
• If Remote Inhibit is used, it should only be connected to the master.
• If
E241
(hardware error) is showing in the status display, the
FUNCTION
switch can be
used to change the configuration
• If there is no communication between units for approximately 10 seconds, all units will
turn off their output and the status display will flash
E241
(hardware error), then
xOFy
where
x
= unit number and
y
= total number of units, and finally the serial/parallel config-
uration setting
SERI
or
PARA
.
3.2.11
UTILITY FUNCTION
The Utility Function provides additional system information or access to special functions.
These are:
•
VERS
- Display System Firmware Version (see PAR. 3.2.11.1)
•
MODL
- Display Model (see PAR. 3.2.11.2)
•
RELY
- Relay Control
•
QkBT
- Quick Boot
•
INVC
- Analog Input Voltage and Current A to D calibration voltages (see PAR. 3.2.11.5)
•
LBT
- Loop Back Test used to isolate RS 232 communication problems (see PAR.
3.4.2.4.
•
CAL
- Display last calibration date and/or begin Calibration (see PAR. 3.2.11.6)
1. If the status display shows
SET
, tap either the
CURRENT
or
VOLTAGE
controls to take the
unit out of setpoint mode (status display goes from
SET
to blank)
2. Using a thin tool (e.g., a paper clip), press the
FUNCTION
switch repeatedly until the status
display shows
UTIL
. Press the
DC OUTPUT
switch to enter the
UTIL
Menu.
3. Rotate either the
VOLTAGE
or
CURRENT
control in either direction to select the function as
identified in the status display as listed above (clockwise selects the functions in the order
described below, counterclockwise reverses the order).
3.2.11.1
DISPLAY SYSTEM FIRMWARE VERSION
Enter
UTIL
menu and rotate either
VOLTAGE
or
CURRENT
control until status display reads
VERS
(see PAR. 3.2.11).
• The
DC VOLTS
display identifies whether the firmware is the factory shipped firmware
(
Pri
displayed) or field updated firmware (
SEC
displayed).
• The
DC AMPS
display shows the firmware version.
Содержание KLP SERIES
Страница 2: ......
Страница 6: ......
Страница 14: ...viii KLP073008 FIGURE 1 1 KLP SERIES POWER SUPPLY...
Страница 20: ...1 6 KLP 073008 FIGURE 1 3 KLP SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING SHEET 1 OF 2 R DWG MECH 3010266...
Страница 21: ...KLP 073008 1 7 FIGURE 1 3 KLP SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING SHEET 2 OF 2...
Страница 26: ......
Страница 40: ......
Страница 86: ......