3-12
KLP073008
NOTE:
Once the relay turns on in
V->C
or
C->V
mode, the relay will go off again when the
unit transitions back to the original mode, or when the output is turned off.
4. When the relay control mode is set to
MAN
, the
DC VOLTS
display shows whether the relay
is ON or OFF. To change the state of the relay press in and rotate either
VOLTAGE
or
CUR-
RENT
control until the desired relay state is displayed, then release the control. Press the
DC OUTPUT
switch to immediately set the relay to the selected state.
5. Press the
DC OUTPUT
switch to exit relay control and advance to the next item in the
UTIL
menu.
NOTE: If a SYSTem:SECurity:IMMediate command is issued, the above relay control settings
are reset to the factory default:
FLT - NORM
.
3.2.11.4
QUICK BOOT
Enter
UTIL
menu and rotate either
VOLTAGE
or
CURRENT
control until status display reads
QkBT
- Quick Boot (see PAR. 3.2.11). If Quick boot is ON, then the next time the unit is powered
up it will go directly to setpoint mode (status display reads
SET
, see PAR. 3.2.6) without display-
ing MODL,VIRT, and PROT settings.
• The
DC VOLTS
display indicates whether quick boot is ON or OFF.
1. Press in and turn either
VOLTAGE
or
CURRENT
control until the desired quick boot state is
displayed,
2. Press
DC OUTPUT
switch to save. The program then advances to the next item in the
UTIL
menu.
3.2.11.5
ANALOG INPUT FULL SCALE CALIBRATION
Enter
UTIL
menu and rotate either
VOLTAGE
or
CURRENT
control until status display reads
INVC
(see PAR. 3.2.11).
• The
DC VOLTS
display shows the analog input voltage value that produces the full
scale output voltage established by the virtual model.
• The
DC AMPS
display shows the analog input voltage value that produces the full scale
output current established by the virtual model.
1. To change the settings tap the
DC OUTPUT
switch.
2. Rotate
VOLTAGE
control to set the analog voltage value required to produce the full scale
output voltage (for fine adjustment press in
VOLTAGE
control and hold while rotating).
3. Rotate the
CURRENT
control to set the analog voltage value required to produce the full
scale output current (for fine adjustment press in
CURRENT
control and hold while rotating).
4. Tap the
DC OUTPUT
switch to accept the new settings or use a thin tool (e.g., a paper clip)
to press the
FUNCTION
switch to cancel the operation.
3.2.11.6
CALIBRATION
Enter
UTIL
menu and rotate either
VOLTAGE
or
CURRENT
control until status display reads
CAL
(see PAR. 3.2.11).
Содержание KLP SERIES
Страница 2: ......
Страница 6: ......
Страница 14: ...viii KLP073008 FIGURE 1 1 KLP SERIES POWER SUPPLY...
Страница 20: ...1 6 KLP 073008 FIGURE 1 3 KLP SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING SHEET 1 OF 2 R DWG MECH 3010266...
Страница 21: ...KLP 073008 1 7 FIGURE 1 3 KLP SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING SHEET 2 OF 2...
Страница 26: ......
Страница 40: ......
Страница 86: ......