Kendrion Kuhnke Automation GmbH
AI 8 Pt/Ni/Tc
201
17 May 2021
Options
You can set up the following options for every channel:
Name
Value
Explanation
SensorType
0
Off (default)
1
Internal (Cold junction)
2
Pt100
3
Pt1000
4
Ni100
5
Ni1000 (DIN43760)
6
Thermo K
7
Thermo J
InputFormat
0
0.1°C
Data rate and
filter
1
Ω / V
2
Raw (raw data)
0
1000 readings per second
Average
1
600 readings per second
2
330 readings per second
3
175 readings per second
4
90 readings per second
5
45 readings per second
6
20 readings per second
7
20 readings per second plus 50 & 60 Hz filter
8
20 readings per second plus 50 Hz filter