Kendrion Kuhnke Automation GmbH
DI16/DO16 LS
41
17 May 2021
Function
The DI16/DO16 LS module features 16 digital low-side inputs and 16 digital low-side outputs.
NOTE
The output drivers have a thermal fuse to automatically turn off any short-circuited outputs. In
case the short circuit prevails, the outputs are allowed to cool down to be turned back on until the
thermal fuse blows again.
Information
The module is not monitored for low voltage states.
Variable
Variable
Data type
Explanation
DigitalInputn
BOOL
Digital input (n=0...15)
DigitalOutputn
BOOL
Digital output (n=0...15)
Technical Data
Digital inputs .................................................. 16
Rising delay ................................................... 1 ms (typically)
Logic level ...................................................... On:
-
3 … 5 V.
Off:
15V … 30V
Input current .................................................. 2mA (typically)
Digital outputs ................................................ 16
Max. current ................................................... 0.5 A each
Max. total current ........................................... 8 A
IO/power connection ......................................
36-pin plug
Controller ....................................................... ASIC ET1200
Baud rate ....................................................... 100 Mbit/s
E-bus connector ............................................ 10-pole system plug in side wall
Terminating module ....................................... not required
Power supply ................................................. 24 VDC -20% +25%
E-bus load...................................................... 135 mA
Part no. .......................................................... 694.450.13
Approval:........................................................