Kendrion Kuhnke Automation GmbH
Safety SDIx SDOx
445
17 May 2021
5.8.4 Kuhnke FIO Safety SDI16 SDO4
There is a separate instruction manual available for Kuhnke FIO Safety I/O. For further information, please
click the link below.
Link to the documentation:
https://productfinder.kuhnke.kendrion.com
Technical Data
Type
Safe input / output terminal
Safety protocol
FSoE
Safety standard
IEC 61508 SIL3 and DIN EN ISO 13849-1 PLe
Number of inputs
16 safe inputs (configurable properties)
Number of outputs
4 safe outputs ( I
max
= 2.0 A)
Clock pulse outputs
(OSSD)
8
Response time
< 1 ms (read input, write to E-bus)
Error response time
≤ watchdog time (configurable)
Extended diagnostic
information
Via CoE
E-bus power consumption Typ. 210 mA (max. 300 mA)
Supply voltage
24 VDC (-15 % / +20 %)
Electrical interference
EN 61000-6-2/EN 61000-6-4
Resistance to vibration
EN 60068-2-6
Impact resistance
EN 60068-2-27
Fieldbus port
EtherCAT
®
100 Mbps LVDS: E-bus
Installation / mounting
position
35 mm DIN rail / horizontal
Signal indication
LEDs per I/O: locally allocated to the terminal point, status LEDs:
EtherCAT, Safety, Power
Shield
Provided directly by the module
Terminals
36-pin spring-assisted connector with mechanical ejector
Ambient conditions
0 °C …+55 °C, IP 20
Housing (W x H x D)
Plastic shroud over aluminium frame, 25 x 120 x 90 [mm]
Approval
CE, EtherCAT Conformance tested, cULus, TÜV Rheinland