1-port RS485
Kendrion Kuhnke Automation GmbH
404
17 May 2021
Response to Errors
EtherCAT error.
Sync Manager watchdog.
LED "Error" flashes 4x.
Unit changes from Op to Safe-Op.
Use "Reset Error" to acknowledge the error.
Out-queue overflow (COM_TxQueueOvr).
Failure to send the data fast enough.
LED "Error" flashes 5x.
Use "Reset Error" to acknowledge the error.
In-queue overflow (COM_RxQueueOvr).
Too much data is being received and cannot be transferred to the control unit fast enough.
LED "Error" flashes 6x.
Use "Reset Error" to acknowledge the error.
TxCount error (TxCounterMiss).
The TxCounter received is not "last TxC 1".
The gateway probably missed an EtherCAT frame. The EtherCAT master is sending the data too
quickly (< 1ms for 9 messages).
LED "Error" flashes 7x.
Use "Reset Error" to acknowledge the error.
Com controller wrror (COM_CtrlErr).
Indicates bit errors or overruns of the control unit concerned.
The applicable LED "COM State" is red and flashes rapidly or alternates green/red while
communicating.
Use "Reset Error" to acknowledge the error.
Object Dictionary
Index
Name
Type
Default
Min Max
Access
1000
Device Type
UINT32
0x191
RO
1001
Error Register
UINT8
RO
1008
Device Name
String
FIO RS485 1 Port
RO
1009
Hardware Version
String
1.00
RO
100A
Software Version
String
1.00
RO
1018
Identity Object
Array
1018, 0
Number of Entries
UINT8
4
RO
1018, 1
Vendor Id
UINT32
0x0048554B
RO
1018, 2
Product Code
UINT32
187270
RO
1018, 3
Revision Number
UINT32
1
RO
1018, 4
Serial Number
UINT32
0
RO
10F1,0
Number of Entries
UINT8
2
RO
10F1,0
Local Error Reaction
UINT32
1
RW
10F1,1
Sync Error Counter Limit
UINT32
4
RW
1600
Receive PDO0 Mapping
Parameter
Array
1600, 0
Number of Entries
UINT8
5
RO
1600, 1
Subindex 001h
UINT32
0x71000010
RO
1600, 2
Subindex 002h
UINT32
0x71010010
RO
1600, 3
Subindex 003h
UINT32
0x71020010
RO