Status LEDs
LED "EtherCAT Run"
The LED labelled "EtherCAT Run" indicates the state of the EtherCAT ASIC.
State
LED flash code
Explanation
Init
Off
Initialising, no data exchange
Pre-Op
Off/green, 1:1
Pre-operational, no data exchange
Safe-Op
Off/green, 5:1
Safe operation, inputs readable
Op
green,
Operational, unrestricted data exchange
Bootstrap
Flickering
Optional if bootstrap mode is supported
LED "IO"
The LED labelled "IO" indicates the state of the module's I/Os.
State
LED flash code
Explanation
Ok
Green, on
No Error
Error
Off
Malfunction of module if E-bus LED = On
Inoperative if E-bus LED = Off
Red, 2 x
Undervoltage
Red, 3 x
Watchdog internal
Red, 4 x
EtherCAT watchdog control
Red, 6 x
Module- specific error, please see details in
Predefined Error Field 0x1003:01 … 08
Red, 7 x
Configuration error (E-bus pre-operational), no. of
process data differs from that in the module
Start, defective Red, on
Module defektiv
LED "Power"
The LED labelled "Power" indicates the state of the I/O module's power supply.
State
LED flash code
Explanation
On
Green, on
24 V DC supply ok
Off
Off
24 V DC supply not ok