Bus Coupler DI16/DO16
Kendrion Kuhnke Automation GmbH
32
17 May 2021
Technical Data
Function ......................................................... Connects a 100 Base-TX EtherCAT with the Kuhnke FIO I/O
modules.
Generates the LVDS system voltages (E-bus)
............................................................. IO module
Controller ....................................................... ASIC ET1100
Baud rate ....................................................... 100 Mbit/s
Cable type...................................................... CAT5
Cable length .................................................. max. 100 m between 2 bus couplers
EtherCAT port ................................................ 2x RJ45
Module power supply ..................................... 24 VDC -15% +20%
IO/power connector ....................................... male 36-pole connector (included in module package)
Input current .................................................. 40 mA & E-bus plus
E-bus power .................................................. max. 2 A (approx. 11 modules)
E-bus connector ............................................ 10-pole system plug in side wall
Terminating module ....................................... not required
Digital inputs .................................................. 16
Rising delay ................................................... 3 ms (typically)
Signal level ....................................................
Off:
-
3V … 5V (EN 61131-3, type 1)
On:
15V … 30V
Digital outputs ................................................ 16
Max. current ................................................... 0.5 A each
Max. total current ........................................... 8 A
Part no. .......................................................... 694.400.10
Approval:........................................................