8  Indoor unit installation 

Kelvinator Air Conditioning

Indoor unit installation

Drain piping

1.   Run the drain hose as shown in figure 6, ensuring it has a 

constant downward fall.

2.   The installer must supply a suitable drain hose extension to run 

from the indoor unit drain hose to the desired drain location. 
The drain hose extension should be fitted and sealed tightly 
with the indoor unit drain hose, and secured in place with vinyl 
tape. Ensure that the drain hose extension also has a continual 
downward fall with an air gap at the bottom, and is drained to 
a suitable location which will not cause damage to people or 
property.

3.   Remove the air filter and pour some water into the drain pan to 

check the water flows smoothly.

Fig 6.

Right

Wrong

No trap is permitted

Do not put the end of 

drain hose into water

Connect the cable to the indoor unit

WARNING

caution

Electrical installation must be completed by suitably qualified 

electrician

Electric safety regulations for the initial installation

1.   If there is serious safety problem about the power supply, 

the technician should refuse to install the air conditioner and 
explain to the client until the problem is solved.

2.   Power voltage should be in the range of 90%–110%  

of rated voltage.

3.   The surge protector and main power switch with a 1.5 times 

capacity of maximum. Current of the unit should be installed in 
power circuit. Ensure the air conditioner is grounded well.

4.   The appliance shall be installed in accordance with national 

wiring regulations.

5.   An all-pole disconnection device which has at least 3mm 

clearances in all poles, the residual current device (RCD) 
having a rated residual operating current not exceeding 30mA, 
and disconnection must be incorporated in the fixed wiring 
in accordance with the wiring rules. Refer to the table for 
recommended circuit breaker rating for normal installation, 
however national and local wiring regulations will prevail.

7.   According to the attached electrical connection diagram 

located on the panel of the indoor and outdoor unit to 
connect the wire.

8.   All wiring must comply with local and national electrical codes 

and be installed by qualified and skilled electricians.

9.   Every wire must be connected firmly. No wire should be 

allowed to touch refrigerant tubing, the compressor, or any 
moving parts.

10.   Loose wiring may cause the terminal to overheat or result in 

unit malfunction. A fire hazard may also exist. Therefore, be 
sure all wiring is tightly connected.

11.   This air conditioner may need to be installed on its own 

separate circuit, please refer to AS/NZS 3000 and local wiring 
regulations for requirements.

12.   For this air conditioner, the main power supply is fed to the 

outdoor unit terminal block, ensure that the main power supply 
wires running to the outdoor unit can carry the full current 
of the air conditioner, which is stated on the rating label, 
according to national wiring regulations. The power and signal 
cable that connects from outdoor unit to indoor unit do not 
carry the full compressor current, therefore 1.0mm

2

 (or larger) is 

suitable for this application.

Содержание KSV25CRG

Страница 1: ...Inverter Air Conditioner Installation Manual KSV25CRG KSV35CRG KSV70CRG KSV25HRG KSD25HRG KSV35HRG KSD35HRG KSV50HRG KSD50HRG KSV70HRG KSD70HRG KSV80HRG KSD80HRG...

Страница 2: ...air conditioner is designed for and intended to be used in normal domestic applications only Record model and serial number here Model number Serial number ENVIRONMENTAL TIPS environment Information...

Страница 3: ...esponsible for their safety Children should be supervised to ensure that they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconnect...

Страница 4: ...inimum room sizes are adhered to for standard installations up to 5m pipe length If larger refrigerant charges than standard are used then please consult AS NZS 60335 2 40 to determine the safe minimu...

Страница 5: ...l Before screwing the remote controller holder to the wall make sure that control signals are properly received by indoor unit 2x AAA batteries In sites with poor drainage use block bases for outdoor...

Страница 6: ...appropriate wall fixings suitable for the wall type being fixed to which is sufficient to support the full weight of the indoor unit 3 Secure the installation plate to the wall with screws NOTE Mount...

Страница 7: ...to drain from both sides another drain pipe will need to be supplied by the installer If choosing one side drainage connection make sure the drain hole on the other side is well plugged For 2 5kW 3 5k...

Страница 8: ...shall be installed in accordance with national wiring regulations 5 An all pole disconnection device which has at least 3mm clearances in all poles the residual current device RCD having a rated resi...

Страница 9: ...lamp Match wire colours with terminal numbers on indoor and outdoor unit terminal blocks and firmly screw wires to the corresponding terminals It is recommended to use the following wire colour sequen...

Страница 10: ...or the outdoor unit with a 8 or 10 diameter bolt and nut tightly and horizontally on a concrete or rigid mount Model Outdoor unit dimensions W x H x D mm Outdoor unit weight kg Dimensions A mm Dimensi...

Страница 11: ...ich also indicates the maximum pipe length and maximum height difference between indoor and outdoor units Please also refer to the below table for discharge and suction pipe diameter Model Discharge p...

Страница 12: ...longer than the pipe length 5 Cut pipes must follow the requirements shown in figure 12 Burr removal 1 Completely remove all burrs from the cut cross section of the pipe 2 Put the end of the copper pi...

Страница 13: ...ally plug the hole in the wall using gum type sealer Indoor unit tubing Flare nut Pipings Fig 16 Fig 17 Outdoor unit electrical connection 1 Check that power supply to the air conditioner circuit is o...

Страница 14: ...lick is heard to confirm it has locked into place Secure the demand response cable in the cable clamp then fit the terminal block cover and secure with screws Outdoor unit installation Magnetic ring i...

Страница 15: ...mum height m Additional refrigerant g m KSV25CRG 6 35 1 4 9 52 3 8 5 25 10 15 KSV35CRG 6 35 1 4 12 7 1 2 5 25 10 15 KSV70CRG 9 52 3 8 15 9 5 8 5 50 25 30 KSV25HRG 6 35 1 4 9 52 3 8 5 25 10 15 KSV35HRG...

Страница 16: ...as pipe side and check that the air is entering Operation noise of the vacuum pump changes and a compound meter indicates 0 instead of minus Then retighten the flare nut 5 Keep the vacuum pump running...

Страница 17: ...over Outdoor unit check point B D C A Fig 22 Operation test After confirming the electrical safety has passed and confirmed there are no gas leaks follow the below steps to complete an operation test...

Страница 18: ...isks NO SMOKING signs shall be displayed Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work A degree of...

Страница 19: ...le for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not be adequate or may need re calibration Detection e...

Страница 20: ...e dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommiss...

Страница 21: ...Kelvinator Air Conditioning Notes 21 Notes...

Страница 22: ...22 Notes Kelvinator Air Conditioning Notes...

Страница 23: ...y unless the defect claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii...

Страница 24: ...r appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux com au web kelvinator com au Ke...

Отзывы: