 Indoor unit installation  7

Indoor unit installation

Drilling the wall

1.   Choose the hole position to be either on the left or right side 

of the installation plate and mark the position according to the 
dimensions shown in figure 2. Note most simple installation is 
with hole on the right side.

2.    Drill the piping hole with a hole core drill of the following 

size: 65mm for models: KSV25CRG, KSV25HRG, KSD25HRG, 
KSV35CRG, KSV35HRG, KSD35HRG 
75mm for models: KSV50HRG, KSD50HRG, KSV70CRG, 
KSV70HRG, KSD70HRG, KSV80HRG, KSD80HRG.

3.    Drill the hole with slight (5-10mm)downward angle from indoor 

to outdoor side so that the outside end is lower than the inside 
end to help drainage, see figure 3.

4.   Insert a wall pipe or other means of protection to prevent the 

pipes and electrical wires from toughing sharp edges within 
the wall.

Connective pipe installation

1.   For the left-hand and right-hand piping, remove the pipe  

cover from the side panel.

2.   For the right back and left back piping, install the piping  

as shown.

 

 NOTE: Bundle the pipes, connecting cable, and drain hose 

with tape securely, evenly as shown in figure 4 on the right.  

The drain connection can be on the right side, left side or 

both. If choosing to drain from both sides, another drain pipe 

will need to be supplied by the installer. If choosing one side 

drainage connection, make sure the drain hole on the other 

side is well plugged. For 2.5kW & 3.5kW models, if choosing 

left-hand or left-back piping, please choosing left side 

drainage connection. The connection of the drain pipe hose 

must be connected by a qualified installer in accordance with 

these instructions to prevent leakage.

3.   Attach the drain hose to the underside of the refrigerant pipes 

with adhesive vinyl tape.

4.   Bundle the pipes, connecting cable, and drain hose with tape 

securely, evenly as shown in Fig. 4.

5.   Pass them through the wall hole.

6.    Ensure that the drain hose has a continual downward fall from 

the indoor side to the outdoor side to ensure the water flows 
out smoothly. Failure to do this can result in water gathering in 
and leaking from the indoor unit.

WARNING

caution

• 

 Do not put anything inside the condensate drain pan (refer to 

figure 5), as this space is required to collect the condensate 

prior to draining out of the indoor unit.

5-10mm

Wall

Outdoor

Indoor

Move and tape 

the drain hose 

with piping in 

a position as 

mentioned in 

Fig. below

Fig. 3

Fig. 4

Fig. 5

Cover for  

the left piping

Cover for  

the piping

Cover for  

the piping

Right piping

Left piping

Left back 

piping

Indoor unit

Condensate 

drain pan

Pipe room

Connective 

pipe
Wrapping 

belt

Drain hose

Connective 

cable

Rubber plug

Содержание KSV25CRG

Страница 1: ...Inverter Air Conditioner Installation Manual KSV25CRG KSV35CRG KSV70CRG KSV25HRG KSD25HRG KSV35HRG KSD35HRG KSV50HRG KSD50HRG KSV70HRG KSD70HRG KSV80HRG KSD80HRG...

Страница 2: ...air conditioner is designed for and intended to be used in normal domestic applications only Record model and serial number here Model number Serial number ENVIRONMENTAL TIPS environment Information...

Страница 3: ...esponsible for their safety Children should be supervised to ensure that they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconnect...

Страница 4: ...inimum room sizes are adhered to for standard installations up to 5m pipe length If larger refrigerant charges than standard are used then please consult AS NZS 60335 2 40 to determine the safe minimu...

Страница 5: ...l Before screwing the remote controller holder to the wall make sure that control signals are properly received by indoor unit 2x AAA batteries In sites with poor drainage use block bases for outdoor...

Страница 6: ...appropriate wall fixings suitable for the wall type being fixed to which is sufficient to support the full weight of the indoor unit 3 Secure the installation plate to the wall with screws NOTE Mount...

Страница 7: ...to drain from both sides another drain pipe will need to be supplied by the installer If choosing one side drainage connection make sure the drain hole on the other side is well plugged For 2 5kW 3 5k...

Страница 8: ...shall be installed in accordance with national wiring regulations 5 An all pole disconnection device which has at least 3mm clearances in all poles the residual current device RCD having a rated resi...

Страница 9: ...lamp Match wire colours with terminal numbers on indoor and outdoor unit terminal blocks and firmly screw wires to the corresponding terminals It is recommended to use the following wire colour sequen...

Страница 10: ...or the outdoor unit with a 8 or 10 diameter bolt and nut tightly and horizontally on a concrete or rigid mount Model Outdoor unit dimensions W x H x D mm Outdoor unit weight kg Dimensions A mm Dimensi...

Страница 11: ...ich also indicates the maximum pipe length and maximum height difference between indoor and outdoor units Please also refer to the below table for discharge and suction pipe diameter Model Discharge p...

Страница 12: ...longer than the pipe length 5 Cut pipes must follow the requirements shown in figure 12 Burr removal 1 Completely remove all burrs from the cut cross section of the pipe 2 Put the end of the copper pi...

Страница 13: ...ally plug the hole in the wall using gum type sealer Indoor unit tubing Flare nut Pipings Fig 16 Fig 17 Outdoor unit electrical connection 1 Check that power supply to the air conditioner circuit is o...

Страница 14: ...lick is heard to confirm it has locked into place Secure the demand response cable in the cable clamp then fit the terminal block cover and secure with screws Outdoor unit installation Magnetic ring i...

Страница 15: ...mum height m Additional refrigerant g m KSV25CRG 6 35 1 4 9 52 3 8 5 25 10 15 KSV35CRG 6 35 1 4 12 7 1 2 5 25 10 15 KSV70CRG 9 52 3 8 15 9 5 8 5 50 25 30 KSV25HRG 6 35 1 4 9 52 3 8 5 25 10 15 KSV35HRG...

Страница 16: ...as pipe side and check that the air is entering Operation noise of the vacuum pump changes and a compound meter indicates 0 instead of minus Then retighten the flare nut 5 Keep the vacuum pump running...

Страница 17: ...over Outdoor unit check point B D C A Fig 22 Operation test After confirming the electrical safety has passed and confirmed there are no gas leaks follow the below steps to complete an operation test...

Страница 18: ...isks NO SMOKING signs shall be displayed Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work A degree of...

Страница 19: ...le for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not be adequate or may need re calibration Detection e...

Страница 20: ...e dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommiss...

Страница 21: ...Kelvinator Air Conditioning Notes 21 Notes...

Страница 22: ...22 Notes Kelvinator Air Conditioning Notes...

Страница 23: ...y unless the defect claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii...

Страница 24: ...r appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux com au web kelvinator com au Ke...

Отзывы: