Kelvinator KSV25CRG Скачать руководство пользователя страница 17

Kelvinator Air Conditioning

 Electrical and gas leak check  17

Electrical and gas leak check

Electrical safety check

Perform the electric safe check after completing installation:

1.   Earth connection - Check the earth connection visually and 

with a multi meter following national wiring rules to confirm 
good earth connection of both the indoor unit and the 
outdoor unit.

2.   Earth leakage test - While the unit is running, conduct earth 

leakage test with a multi meter. If high leakage current is 
detected immediately switch off the unit and solve the 
problem before proceeding. Follow earth leakage test 
procedure as per national wiring rules.

Gas leak check

1.   Soap water method: Apply a soap water or a liquid neutral 

detergent on the indoor unit connections and outdoor unit 
connections by a soft brush to check for leakage of the 
connecting points of the piping. If bubbles come out, it 
indicates that the pipes have leakage. 

2.   Leak detector method: Use a leak detector to check near 

connections A, B, C & D for refrigerant leakage.

Indoor unit  

check point

Cover

Outdoor unit 

check point

B

D

C

A

Fig. 22

Operation test

After confirming the electrical safety has passed and confirmed 
there are no gas leaks, follow the below steps to complete an 
operation test:

Check that all tubing and wiring have been properly connected.

Check that the gas and liquid side service valves are fully open.

1.   Connect the power, press the ON/OFF button on the remote 

controller to turn the unit on.

2.   Use the MODE button to select COOL, HEAT, AUTO and FAN 

to check if all the functions work well.

3.   When the ambient temperature is too low (lower than 17°C), 

the unit cannot be controlled by the remote controller to run in 
cooling mode. Force the unit into cooling mode by using the 
manual control button on the indoor unit as per below. 

• 

 Hold the panel sides and lift the panel up to an angle until it 
remains fixed with a clicking sound.

• 

 Pressing the button once will put the unit into AUTO mode, 
and the unit will automatically select heating or cooling based 
on the ambient room conditions. Pressing the button twice 
within 5 seconds to put the unit into forced cooling mode. 
Pressing the button while the unit is operating will switch off 
the unit.

4.  The test operation should last about 30 minutes.

Auto/Cool

Manual control

button

Содержание KSV25CRG

Страница 1: ...Inverter Air Conditioner Installation Manual KSV25CRG KSV35CRG KSV70CRG KSV25HRG KSD25HRG KSV35HRG KSD35HRG KSV50HRG KSD50HRG KSV70HRG KSD70HRG KSV80HRG KSD80HRG...

Страница 2: ...air conditioner is designed for and intended to be used in normal domestic applications only Record model and serial number here Model number Serial number ENVIRONMENTAL TIPS environment Information...

Страница 3: ...esponsible for their safety Children should be supervised to ensure that they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconnect...

Страница 4: ...inimum room sizes are adhered to for standard installations up to 5m pipe length If larger refrigerant charges than standard are used then please consult AS NZS 60335 2 40 to determine the safe minimu...

Страница 5: ...l Before screwing the remote controller holder to the wall make sure that control signals are properly received by indoor unit 2x AAA batteries In sites with poor drainage use block bases for outdoor...

Страница 6: ...appropriate wall fixings suitable for the wall type being fixed to which is sufficient to support the full weight of the indoor unit 3 Secure the installation plate to the wall with screws NOTE Mount...

Страница 7: ...to drain from both sides another drain pipe will need to be supplied by the installer If choosing one side drainage connection make sure the drain hole on the other side is well plugged For 2 5kW 3 5k...

Страница 8: ...shall be installed in accordance with national wiring regulations 5 An all pole disconnection device which has at least 3mm clearances in all poles the residual current device RCD having a rated resi...

Страница 9: ...lamp Match wire colours with terminal numbers on indoor and outdoor unit terminal blocks and firmly screw wires to the corresponding terminals It is recommended to use the following wire colour sequen...

Страница 10: ...or the outdoor unit with a 8 or 10 diameter bolt and nut tightly and horizontally on a concrete or rigid mount Model Outdoor unit dimensions W x H x D mm Outdoor unit weight kg Dimensions A mm Dimensi...

Страница 11: ...ich also indicates the maximum pipe length and maximum height difference between indoor and outdoor units Please also refer to the below table for discharge and suction pipe diameter Model Discharge p...

Страница 12: ...longer than the pipe length 5 Cut pipes must follow the requirements shown in figure 12 Burr removal 1 Completely remove all burrs from the cut cross section of the pipe 2 Put the end of the copper pi...

Страница 13: ...ally plug the hole in the wall using gum type sealer Indoor unit tubing Flare nut Pipings Fig 16 Fig 17 Outdoor unit electrical connection 1 Check that power supply to the air conditioner circuit is o...

Страница 14: ...lick is heard to confirm it has locked into place Secure the demand response cable in the cable clamp then fit the terminal block cover and secure with screws Outdoor unit installation Magnetic ring i...

Страница 15: ...mum height m Additional refrigerant g m KSV25CRG 6 35 1 4 9 52 3 8 5 25 10 15 KSV35CRG 6 35 1 4 12 7 1 2 5 25 10 15 KSV70CRG 9 52 3 8 15 9 5 8 5 50 25 30 KSV25HRG 6 35 1 4 9 52 3 8 5 25 10 15 KSV35HRG...

Страница 16: ...as pipe side and check that the air is entering Operation noise of the vacuum pump changes and a compound meter indicates 0 instead of minus Then retighten the flare nut 5 Keep the vacuum pump running...

Страница 17: ...over Outdoor unit check point B D C A Fig 22 Operation test After confirming the electrical safety has passed and confirmed there are no gas leaks follow the below steps to complete an operation test...

Страница 18: ...isks NO SMOKING signs shall be displayed Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work A degree of...

Страница 19: ...le for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not be adequate or may need re calibration Detection e...

Страница 20: ...e dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommiss...

Страница 21: ...Kelvinator Air Conditioning Notes 21 Notes...

Страница 22: ...22 Notes Kelvinator Air Conditioning Notes...

Страница 23: ...y unless the defect claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii...

Страница 24: ...r appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux com au web kelvinator com au Ke...

Отзывы: