 Outdoor unit installation  13

Outdoor unit installation

Tightening Connection

• 

 Align the center of the pipes.  

• 

 Sufficiently tighten the flare nut with fingers, and then tighten it 
with a spanner and torque wrench as shown in Fig.16 & 17.

Outer diameter (mm)

Torque (N.cm)

ø 6.35 (1/4")

15-20

ø 9.52 (3/8")

35-40

ø 12.7 (1/2")

50-55

ø 15.9 (5/8")

60-65

WARNING

caution

• 

 Excessive torque can break the nut or flared pipe and cause 
a leak, and too low torque can also cause a leak. Follow the 
specified torque and use a torque wrench as required.

• 

 When flared joints are reused, the flare part shall be  
re-fabricated.

• 

 Neatly run the refrigeration pipe from the indoor unit 
connection to the outdoor unit suction and discharge 
connections. Follow the same flaring procedure outlined 
above to flare and connect the suction and discharge pipes to 
the outdoor unit accordingly.

Insulating the pipes

Wrap suitable insulation material (supplied by the installer) separately 
around each individual refrigeration pipe, the suction and discharge 
pipes must not be in direct contact. Ensure that the flare connections 
are covered, then wrap the insulated pipes with vinyl tape. 

Attach the interconnecting electrical cable and drain pipe to 
the pipe assembly with narrow vinyl tape, then wrap the whole 
assembly with wide vinyl tape starting from top to bottom, as 
pictured in the diagram below.

Finally plug the hole in the wall using gum type sealer.

Indoor unit tubing

Flare nut

Pipings

Fig. 16

Fig. 17

Outdoor unit electrical connection

1.   Check that power supply to the air conditioner circuit is off

2.   Confirm that power cable with suitable rating for the air 

conditioner current rating has been run from the circuit breaker 
to the isolation switch, according to AS/NZS 3000 & local 
wiring rules.

3.   Run power supply cable from the isolation switch to the 

outdoor unit terminal block area. Also run the interconnecting 
cables from the indoor unit to the outdoor unit terminal 
block area. All exposed power cables must be protected, for 
example in conduit.

4.   Remove the terminal block cover and loosen the cable clamp 

as shown in figure 18.

Terminal block

Cover

Screw (1–2 model 

dependant)

Cable clamp

Fig. 18

5.   Connect the interconnecting cable from the indoor unit to the 

terminal block following the below wiring diagram, ensuring 
that the colours match between indoor unit and outdoor unit.

6.   Connect the main power supply cables from the isolation 

switch to the outdoor unit terminal block following the wiring 
diagram.

7.    Ensure that the terminal block screws are secure by gently 

pulling the wires.

8.   Fit the cable clamp over the incoming wires to protect from 

strain, then fit the cover and fix in place with the screw.

suction line pipe

liquid line pipe

connection pipe

wrap with vinyl tape

indoor pipe unit

pipe

vinyl tape

(narrow) 

wrap with vinyl

tape (wide)

pipe

vinyl tape (wide)

connection 

cable

vinyl tape  

(narrow)

drain hose

connection

power cable

incorrect

heat insulation

Содержание KSV25CRG

Страница 1: ...Inverter Air Conditioner Installation Manual KSV25CRG KSV35CRG KSV70CRG KSV25HRG KSD25HRG KSV35HRG KSD35HRG KSV50HRG KSD50HRG KSV70HRG KSD70HRG KSV80HRG KSD80HRG...

Страница 2: ...air conditioner is designed for and intended to be used in normal domestic applications only Record model and serial number here Model number Serial number ENVIRONMENTAL TIPS environment Information...

Страница 3: ...esponsible for their safety Children should be supervised to ensure that they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconnect...

Страница 4: ...inimum room sizes are adhered to for standard installations up to 5m pipe length If larger refrigerant charges than standard are used then please consult AS NZS 60335 2 40 to determine the safe minimu...

Страница 5: ...l Before screwing the remote controller holder to the wall make sure that control signals are properly received by indoor unit 2x AAA batteries In sites with poor drainage use block bases for outdoor...

Страница 6: ...appropriate wall fixings suitable for the wall type being fixed to which is sufficient to support the full weight of the indoor unit 3 Secure the installation plate to the wall with screws NOTE Mount...

Страница 7: ...to drain from both sides another drain pipe will need to be supplied by the installer If choosing one side drainage connection make sure the drain hole on the other side is well plugged For 2 5kW 3 5k...

Страница 8: ...shall be installed in accordance with national wiring regulations 5 An all pole disconnection device which has at least 3mm clearances in all poles the residual current device RCD having a rated resi...

Страница 9: ...lamp Match wire colours with terminal numbers on indoor and outdoor unit terminal blocks and firmly screw wires to the corresponding terminals It is recommended to use the following wire colour sequen...

Страница 10: ...or the outdoor unit with a 8 or 10 diameter bolt and nut tightly and horizontally on a concrete or rigid mount Model Outdoor unit dimensions W x H x D mm Outdoor unit weight kg Dimensions A mm Dimensi...

Страница 11: ...ich also indicates the maximum pipe length and maximum height difference between indoor and outdoor units Please also refer to the below table for discharge and suction pipe diameter Model Discharge p...

Страница 12: ...longer than the pipe length 5 Cut pipes must follow the requirements shown in figure 12 Burr removal 1 Completely remove all burrs from the cut cross section of the pipe 2 Put the end of the copper pi...

Страница 13: ...ally plug the hole in the wall using gum type sealer Indoor unit tubing Flare nut Pipings Fig 16 Fig 17 Outdoor unit electrical connection 1 Check that power supply to the air conditioner circuit is o...

Страница 14: ...lick is heard to confirm it has locked into place Secure the demand response cable in the cable clamp then fit the terminal block cover and secure with screws Outdoor unit installation Magnetic ring i...

Страница 15: ...mum height m Additional refrigerant g m KSV25CRG 6 35 1 4 9 52 3 8 5 25 10 15 KSV35CRG 6 35 1 4 12 7 1 2 5 25 10 15 KSV70CRG 9 52 3 8 15 9 5 8 5 50 25 30 KSV25HRG 6 35 1 4 9 52 3 8 5 25 10 15 KSV35HRG...

Страница 16: ...as pipe side and check that the air is entering Operation noise of the vacuum pump changes and a compound meter indicates 0 instead of minus Then retighten the flare nut 5 Keep the vacuum pump running...

Страница 17: ...over Outdoor unit check point B D C A Fig 22 Operation test After confirming the electrical safety has passed and confirmed there are no gas leaks follow the below steps to complete an operation test...

Страница 18: ...isks NO SMOKING signs shall be displayed Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work A degree of...

Страница 19: ...le for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not be adequate or may need re calibration Detection e...

Страница 20: ...e dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommiss...

Страница 21: ...Kelvinator Air Conditioning Notes 21 Notes...

Страница 22: ...22 Notes Kelvinator Air Conditioning Notes...

Страница 23: ...y unless the defect claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii...

Страница 24: ...r appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux com au web kelvinator com au Ke...

Отзывы: