12  Outdoor unit installation 

Kelvinator Air Conditioning

Flaring work

TIPS & INFORMATION

 important

For installer 

It is critical that the installer follows the correct flaring procedure 

using the right tools to produce good quality flares in order to 

ensure installation without refrigerant gas leaks. 

Service calls caused by poor installation are the responsibility of 

the installer, and these service calls will be referred back to the 

installer accordingly. 

Please take care to make the flare connection carefully and test for 
refrigerant leaks before commissioning the air conditioner.

Main cause for refrigerant leakage is due to defect in the flaring 
work. Carry out correct flaring work using the following procedure:

Cut the pipes and the cable

1.   Purchase the appropriate pipe size locally according to the 

table on page 11.

2.   Measure the distance between the indoor and the  

outdoor unit.

3.  Cut the pipes a little longer than the measured distance.

4.  Cut the cable 1.5m longer than the pipe length.

5.  Cut pipes must follow the requirements shown in figure 12.

Burr removal

1.   Completely remove all burrs from the cut cross section  

of the pipe.

2.   Put the end of the copper pipe in a downward direction as you 

remove burrs in order to avoid dropping burrs into  
the the pipe, as shown in figure 13.

WARNING

caution

Putting nut on

Remove flare nuts attached to indoor and outdoor unit, then put 
them on pipe/tube having completed burr removal (not possible to 
put them on after flaring work).

Flaring work

Carry out flaring work using a flaring tool as shown in figure 15, and 

ensure dimension A is maintained within the tolerance as indicated 

in the table below.

Outer diameter (mm)

Dimension A (mm) as per fig. 15
Max.

Min.

ø 6.35 (1/4") 

1.3

0.7

ø 9.52 (3/8") 

1.6

1.0

ø 12.7 (1/2") 

1.8

1.0

ø 15.9 (5/8") 

2.4

2.2

"

90°

Oblique

Fig. 12

Fig. 13

Fig. 14

Point down

Copper tube

Flare nut

Pipe

Reamer

Roughness

Burr

Checking flare work

Compare the flare work with the adjacent diagram. If the pipe has 
any defect, cut off the flared section and redo the flare until it meets 
the requirements.

Fig. 15 

Bar

Copper 

pipe

Clamp 

handle

Bar

Handle

Yoke

Cone

Red arrow mark

A

Outdoor unit installation

Содержание KSV25CRG

Страница 1: ...Inverter Air Conditioner Installation Manual KSV25CRG KSV35CRG KSV70CRG KSV25HRG KSD25HRG KSV35HRG KSD35HRG KSV50HRG KSD50HRG KSV70HRG KSD70HRG KSV80HRG KSD80HRG...

Страница 2: ...air conditioner is designed for and intended to be used in normal domestic applications only Record model and serial number here Model number Serial number ENVIRONMENTAL TIPS environment Information...

Страница 3: ...esponsible for their safety Children should be supervised to ensure that they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconnect...

Страница 4: ...inimum room sizes are adhered to for standard installations up to 5m pipe length If larger refrigerant charges than standard are used then please consult AS NZS 60335 2 40 to determine the safe minimu...

Страница 5: ...l Before screwing the remote controller holder to the wall make sure that control signals are properly received by indoor unit 2x AAA batteries In sites with poor drainage use block bases for outdoor...

Страница 6: ...appropriate wall fixings suitable for the wall type being fixed to which is sufficient to support the full weight of the indoor unit 3 Secure the installation plate to the wall with screws NOTE Mount...

Страница 7: ...to drain from both sides another drain pipe will need to be supplied by the installer If choosing one side drainage connection make sure the drain hole on the other side is well plugged For 2 5kW 3 5k...

Страница 8: ...shall be installed in accordance with national wiring regulations 5 An all pole disconnection device which has at least 3mm clearances in all poles the residual current device RCD having a rated resi...

Страница 9: ...lamp Match wire colours with terminal numbers on indoor and outdoor unit terminal blocks and firmly screw wires to the corresponding terminals It is recommended to use the following wire colour sequen...

Страница 10: ...or the outdoor unit with a 8 or 10 diameter bolt and nut tightly and horizontally on a concrete or rigid mount Model Outdoor unit dimensions W x H x D mm Outdoor unit weight kg Dimensions A mm Dimensi...

Страница 11: ...ich also indicates the maximum pipe length and maximum height difference between indoor and outdoor units Please also refer to the below table for discharge and suction pipe diameter Model Discharge p...

Страница 12: ...longer than the pipe length 5 Cut pipes must follow the requirements shown in figure 12 Burr removal 1 Completely remove all burrs from the cut cross section of the pipe 2 Put the end of the copper pi...

Страница 13: ...ally plug the hole in the wall using gum type sealer Indoor unit tubing Flare nut Pipings Fig 16 Fig 17 Outdoor unit electrical connection 1 Check that power supply to the air conditioner circuit is o...

Страница 14: ...lick is heard to confirm it has locked into place Secure the demand response cable in the cable clamp then fit the terminal block cover and secure with screws Outdoor unit installation Magnetic ring i...

Страница 15: ...mum height m Additional refrigerant g m KSV25CRG 6 35 1 4 9 52 3 8 5 25 10 15 KSV35CRG 6 35 1 4 12 7 1 2 5 25 10 15 KSV70CRG 9 52 3 8 15 9 5 8 5 50 25 30 KSV25HRG 6 35 1 4 9 52 3 8 5 25 10 15 KSV35HRG...

Страница 16: ...as pipe side and check that the air is entering Operation noise of the vacuum pump changes and a compound meter indicates 0 instead of minus Then retighten the flare nut 5 Keep the vacuum pump running...

Страница 17: ...over Outdoor unit check point B D C A Fig 22 Operation test After confirming the electrical safety has passed and confirmed there are no gas leaks follow the below steps to complete an operation test...

Страница 18: ...isks NO SMOKING signs shall be displayed Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work A degree of...

Страница 19: ...le for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not be adequate or may need re calibration Detection e...

Страница 20: ...e dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommiss...

Страница 21: ...Kelvinator Air Conditioning Notes 21 Notes...

Страница 22: ...22 Notes Kelvinator Air Conditioning Notes...

Страница 23: ...y unless the defect claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii...

Страница 24: ...r appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux com au web kelvinator com au Ke...

Отзывы: