Kelvinator KSV25CRG Скачать руководство пользователя страница 15

Kelvinator Air Conditioning

 Test running  15

Test running

Air purging

Air and other foreign matter in the refrigerant circuit causes 
abnormal pressure rise, which may result in equipment damage 
and even injury. Therefore, the indoor unit and tubing between 
the indoor and outdoor unit must be leak tested and evacuated to 
remove any non condensable and moisture from the system.

NOTE: Any brazed connections must be completed before 

evacuation and prior to release of any refrigerant into the 

refrigeration system. Low temperature solder must not be used.

Air purging with vacuum pump

• 

 Preparation   
Check that each tube (both liquid and gas side tubes) between 
the indoor and outdoor units have been properly connected 
and all wiring for the test run has been completed. Remove 
the service valve caps from both the gas and the liquid side on 
the outdoor unit. Note that both the liquid and the gas side 
service valves on the outdoor unit are kept closed at this stage.

• 

Pipe length and refrigerant amount:

Model 
number

Discharge 
pipe diameter

Suction pipe 
diameter

Standard 
length (m)

Maximum 
length (m)

Maximum 
height (m)

Additional 
refrigerant (g/m)

KSV25CRG

ø 6.35 (1/4") 

ø 9.52 (3/8") 

5

25

10

15

KSV35CRG

ø 6.35 (1/4") 

ø 12.7 (1/2") 

5

25

10

15

KSV70CRG

ø 9.52 (3/8") 

ø 15.9 (5/8") 

5

50

25

30

KSV25HRG

ø 6.35 (1/4") 

ø 9.52 (3/8") 

5

25

10

15

KSV35HRG

ø 6.35 (1/4") 

ø 12.7 (1/2") 

5

25

10

15

KSV50HRG

ø 6.35 (1/4") 

ø 12.7 (1/2") 

5

30

20

15

KSV70HRG

ø 9.52 (3/8") 

ø 15.9 (5/8")

5

50

25

30

KSV80HRG

ø 9.52 (3/8") 

ø 15.9 (5/8")

5

50

25

30

KSD25HRG

ø 6.35 (1/4") 

ø 9.52 (3/8") 

5

25

10

15

KSD35HRG

ø 6.35 (1/4") 

 12.7 (1/2")

5

25

10

15

KSD50HRG

ø 6.35 (1/4") 

 12.7 (1/2")

5

30

20

15

KSD70HRG

ø 9.52 (3/8") 

ø 15.9 (5/8")

5

50

25

30

KSD80HRG

ø 9.52 (3/8") 

ø 15.9 (5/8")

5

50

25

30

Additional refrigerant required for pipe length greater than 
standard 5m installation can be calculated using the following 
equation:
M = (L - 5) x A
Where:
M = Mass of additional refrigerant (g)
L = Actual installed connecting pipe length (m)
A = Additional refrigerant required per meter of connecting pipe 
(g/m) (refer to the above table)

WARNING

caution

R32 is a mildly flammable refrigerant. Make sure that the area has 

been made safe by having suitable ventilation and is free from 

ignition sources before charging or releasing the charge of R32.

WARNING

warning

If additional refrigerant charge is added, please check the 

minimum indoor room size for the complete air conditioner 

R32 charge has been checked and complied with against the 

requirements of AS/NZS 60335.2.40

Содержание KSV25CRG

Страница 1: ...Inverter Air Conditioner Installation Manual KSV25CRG KSV35CRG KSV70CRG KSV25HRG KSD25HRG KSV35HRG KSD35HRG KSV50HRG KSD50HRG KSV70HRG KSD70HRG KSV80HRG KSD80HRG...

Страница 2: ...air conditioner is designed for and intended to be used in normal domestic applications only Record model and serial number here Model number Serial number ENVIRONMENTAL TIPS environment Information...

Страница 3: ...esponsible for their safety Children should be supervised to ensure that they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconnect...

Страница 4: ...inimum room sizes are adhered to for standard installations up to 5m pipe length If larger refrigerant charges than standard are used then please consult AS NZS 60335 2 40 to determine the safe minimu...

Страница 5: ...l Before screwing the remote controller holder to the wall make sure that control signals are properly received by indoor unit 2x AAA batteries In sites with poor drainage use block bases for outdoor...

Страница 6: ...appropriate wall fixings suitable for the wall type being fixed to which is sufficient to support the full weight of the indoor unit 3 Secure the installation plate to the wall with screws NOTE Mount...

Страница 7: ...to drain from both sides another drain pipe will need to be supplied by the installer If choosing one side drainage connection make sure the drain hole on the other side is well plugged For 2 5kW 3 5k...

Страница 8: ...shall be installed in accordance with national wiring regulations 5 An all pole disconnection device which has at least 3mm clearances in all poles the residual current device RCD having a rated resi...

Страница 9: ...lamp Match wire colours with terminal numbers on indoor and outdoor unit terminal blocks and firmly screw wires to the corresponding terminals It is recommended to use the following wire colour sequen...

Страница 10: ...or the outdoor unit with a 8 or 10 diameter bolt and nut tightly and horizontally on a concrete or rigid mount Model Outdoor unit dimensions W x H x D mm Outdoor unit weight kg Dimensions A mm Dimensi...

Страница 11: ...ich also indicates the maximum pipe length and maximum height difference between indoor and outdoor units Please also refer to the below table for discharge and suction pipe diameter Model Discharge p...

Страница 12: ...longer than the pipe length 5 Cut pipes must follow the requirements shown in figure 12 Burr removal 1 Completely remove all burrs from the cut cross section of the pipe 2 Put the end of the copper pi...

Страница 13: ...ally plug the hole in the wall using gum type sealer Indoor unit tubing Flare nut Pipings Fig 16 Fig 17 Outdoor unit electrical connection 1 Check that power supply to the air conditioner circuit is o...

Страница 14: ...lick is heard to confirm it has locked into place Secure the demand response cable in the cable clamp then fit the terminal block cover and secure with screws Outdoor unit installation Magnetic ring i...

Страница 15: ...mum height m Additional refrigerant g m KSV25CRG 6 35 1 4 9 52 3 8 5 25 10 15 KSV35CRG 6 35 1 4 12 7 1 2 5 25 10 15 KSV70CRG 9 52 3 8 15 9 5 8 5 50 25 30 KSV25HRG 6 35 1 4 9 52 3 8 5 25 10 15 KSV35HRG...

Страница 16: ...as pipe side and check that the air is entering Operation noise of the vacuum pump changes and a compound meter indicates 0 instead of minus Then retighten the flare nut 5 Keep the vacuum pump running...

Страница 17: ...over Outdoor unit check point B D C A Fig 22 Operation test After confirming the electrical safety has passed and confirmed there are no gas leaks follow the below steps to complete an operation test...

Страница 18: ...isks NO SMOKING signs shall be displayed Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work A degree of...

Страница 19: ...le for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not be adequate or may need re calibration Detection e...

Страница 20: ...e dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommiss...

Страница 21: ...Kelvinator Air Conditioning Notes 21 Notes...

Страница 22: ...22 Notes Kelvinator Air Conditioning Notes...

Страница 23: ...y unless the defect claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii...

Страница 24: ...r appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux com au web kelvinator com au Ke...

Отзывы: