Kelvinator KSV25CRG Скачать руководство пользователя страница 19

Kelvinator Air Conditioning

 Information servicing  19

Information servicing

Repairs to sealed components

1.   During repairs to sealed components, all electrical supplies 

shall be disconnected from the equipment being worked upon 
prior to any removal of sealed covers, etc. If it is absolutely 
necessary to have an electrical supply to equipment during 
servicing, then a permanently operating form of leak detection 
shall be located at the most critical point to warn of a 
potentially hazardous situation. 

2.   Particular attention shall be paid to the following to ensure that 

by working on electrical components, the casing is not altered 
in such a way that the level of protection is affected. This shall 
include damage to cables, excessive number of connections, 
terminals not made to original specification, damage to seals, 
incorrect fitting of glands, etc. 

• 

 Ensure that apparatus is mounted securely. 

• 

 Ensure that seals or sealing materials have not degraded 
such that they no longer serve the purpose of preventing the 
ingress of flammable atmospheres. Replacement parts shall be 
in accordance with the manufacturer's specifications.

NOTE: The use of silicon sealant may inhibit the effectiveness 

of some types of leak detection equipment. Intrinsically safe 

components do not have to be isolated prior to working on them.

Repair to intrinsically safe components

Do not apply any permanent inductive or capacitance loads to the 
circuit without ensuring that this will not exceed the permissible 
voltage and current permitted for the equipment in use. Intrinsically 
safe components are the only types that can be worked on while 
live in the presence of a flammable atmosphere. The test apparatus 
shall be at the correct rating. Replace components only with parts 
specified by the manufacturer. Other parts may result in the ignition 
of refrigerant in the atmosphere from a leak.

Cabling

Check that cabling will not be subject to wear, corrosion, 
excessive pressure, vibration, sharp edges or any other adverse 
environmental effects. The check shall also take into account 
the effects of aging or continual vibration from sources such as 
compressors or fans.

Leak detection methods

The following leak detection methods are deemed acceptable 
for systems containing flammable refrigerants. Electronic leak 
detectors shall be used to detect flammable refrigerants, but 
the sensitivity may not be adequate, or may need re-calibration. 
(Detection equipment shall be calibrated in a refrigerant-free 
area.) Ensure that the detector is not a potential source of ignition 
and is suitable for the refrigerant used. Leak detection equipment 
shall be set at a percentage of the LFL of the refrigerant and shall 
be calibrated to the refrigerant employed and the appropriate 
percentage of gas (25 % maximum) is confirmed. Leak detection 
fluids are suitable for use with most refrigerants but the use of 
detergents containing chlorine shall be avoided as the chlorine 
may react with the refrigerant and corrode the copper pipe-
work. If a leak is suspected, all naked flames shall be removed or 
extinguished. If a leakage of refrigerant is found which requires 
brazing, all of the refrigerant shall be recovered from the system, or 
isolated (by means of shut off valves) in a part of the system remote 
from the leak. Oxygen free nitrogen (OFN) shall then be purged 
through the system both before and during the brazing process.

Removal and evacuation

When breaking into the refrigerant circuit to make repairs or for any 
other purpose conventional procedures shall be used. However, 
it is important that best practice is followed since flammability is a 
consideration. The following procedure shall be adhered to 

• 

 Remove  refrigerant;

• 

 Purge the circuit with inert gas;

• 

 Evacuate;

• 

 Purge again with inert gas;

• 

 Open the circuit by cutting or brazing.

The refrigerant charge shall be recovered into the correct recovery 
cylinders. The system shall be flushed with OFN to render the 
unit safe. This process may need to be repeated several times. 
Compressed air or oxygen shall not be used for this task. Flushing 
shall be achieved by breaking the vacuum in the system with OFN 
and continuing to fill until the working pressure is achieved, then 
venting to atmosphere, and finally pulling down to a vacuum. This 
process shall be repeated until no refrigerant is within the system. 
When the final OFN charge is used, the system shall be vented 
down to atmospheric pressure to enable work to take place. This 
operation is absolutely vital if brazing operations on the pipe-work 
are to take place. Ensure that the outlet for the vacuum pump is not 
close to any ignition sources and there is ventilation available.

Содержание KSV25CRG

Страница 1: ...Inverter Air Conditioner Installation Manual KSV25CRG KSV35CRG KSV70CRG KSV25HRG KSD25HRG KSV35HRG KSD35HRG KSV50HRG KSD50HRG KSV70HRG KSD70HRG KSV80HRG KSD80HRG...

Страница 2: ...air conditioner is designed for and intended to be used in normal domestic applications only Record model and serial number here Model number Serial number ENVIRONMENTAL TIPS environment Information...

Страница 3: ...esponsible for their safety Children should be supervised to ensure that they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconnect...

Страница 4: ...inimum room sizes are adhered to for standard installations up to 5m pipe length If larger refrigerant charges than standard are used then please consult AS NZS 60335 2 40 to determine the safe minimu...

Страница 5: ...l Before screwing the remote controller holder to the wall make sure that control signals are properly received by indoor unit 2x AAA batteries In sites with poor drainage use block bases for outdoor...

Страница 6: ...appropriate wall fixings suitable for the wall type being fixed to which is sufficient to support the full weight of the indoor unit 3 Secure the installation plate to the wall with screws NOTE Mount...

Страница 7: ...to drain from both sides another drain pipe will need to be supplied by the installer If choosing one side drainage connection make sure the drain hole on the other side is well plugged For 2 5kW 3 5k...

Страница 8: ...shall be installed in accordance with national wiring regulations 5 An all pole disconnection device which has at least 3mm clearances in all poles the residual current device RCD having a rated resi...

Страница 9: ...lamp Match wire colours with terminal numbers on indoor and outdoor unit terminal blocks and firmly screw wires to the corresponding terminals It is recommended to use the following wire colour sequen...

Страница 10: ...or the outdoor unit with a 8 or 10 diameter bolt and nut tightly and horizontally on a concrete or rigid mount Model Outdoor unit dimensions W x H x D mm Outdoor unit weight kg Dimensions A mm Dimensi...

Страница 11: ...ich also indicates the maximum pipe length and maximum height difference between indoor and outdoor units Please also refer to the below table for discharge and suction pipe diameter Model Discharge p...

Страница 12: ...longer than the pipe length 5 Cut pipes must follow the requirements shown in figure 12 Burr removal 1 Completely remove all burrs from the cut cross section of the pipe 2 Put the end of the copper pi...

Страница 13: ...ally plug the hole in the wall using gum type sealer Indoor unit tubing Flare nut Pipings Fig 16 Fig 17 Outdoor unit electrical connection 1 Check that power supply to the air conditioner circuit is o...

Страница 14: ...lick is heard to confirm it has locked into place Secure the demand response cable in the cable clamp then fit the terminal block cover and secure with screws Outdoor unit installation Magnetic ring i...

Страница 15: ...mum height m Additional refrigerant g m KSV25CRG 6 35 1 4 9 52 3 8 5 25 10 15 KSV35CRG 6 35 1 4 12 7 1 2 5 25 10 15 KSV70CRG 9 52 3 8 15 9 5 8 5 50 25 30 KSV25HRG 6 35 1 4 9 52 3 8 5 25 10 15 KSV35HRG...

Страница 16: ...as pipe side and check that the air is entering Operation noise of the vacuum pump changes and a compound meter indicates 0 instead of minus Then retighten the flare nut 5 Keep the vacuum pump running...

Страница 17: ...over Outdoor unit check point B D C A Fig 22 Operation test After confirming the electrical safety has passed and confirmed there are no gas leaks follow the below steps to complete an operation test...

Страница 18: ...isks NO SMOKING signs shall be displayed Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work A degree of...

Страница 19: ...le for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not be adequate or may need re calibration Detection e...

Страница 20: ...e dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommiss...

Страница 21: ...Kelvinator Air Conditioning Notes 21 Notes...

Страница 22: ...22 Notes Kelvinator Air Conditioning Notes...

Страница 23: ...y unless the defect claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii...

Страница 24: ...r appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux com au web kelvinator com au Ke...

Отзывы: