Purge Gas Supply Notes

An alarm shall be provided to indicate failure of the protective gas supply to maintain the required pressure . Piping for 
the protective gas shall be protected against mechanical damage .
Where the compressor intake line passes through a classified location, it shall be constructed of noncombustible 
material, designed to prevent leakage of flammable gases, vapors, or dusts into the protective gas, and protected 
against mechanical damage and corrosion .
The electrical power for the protective gas supply (blower, compressor, etc .) shall be supplied either from a separate 
power source or from the protected enclosure power supply prior to any service disconnects of the protected 
enclosure . Any protected enclosure that can be isolated from the protective gas supply shall be equipped with an 
alarm . Where an alarm is used to indicate the loss of pressure in the cabinet:

•  The alarm shall be located at a constantly attended location .
•  The alarm actuator shall take its signal from the protected enclosure and shall not be installed between the 

enclosure and the protective gas supply .

•  The alarm actuator shall be mechanical, pneumatic, or electrical .
•  Electrical alarms and electrical alarm actuators shall be approved for the location in which they are installed .
•  No valves shall be permitted between the alarm actuator and the enclosure .

Intrinsically Safe (IS) Installation

1 .  Electrical equipment connected to associated apparatus should not use or generate more than 250 volts .
2 .  Installation shall be in accordance with the manufacturer's instructions and the National Electrical Code  

(NFPA 70)

3 .  For guidance on Installation see ANSI/ISA RP12 .6 (Installation of IS Instrument System in Class I 

Hazardous Locations) .

4 .  Voc or Vt of associated apparatus is less than Vmax 

Isc or IT of associated apparatus is less than Imax 
Ci plus capacitance of interconnecting cabling is less than Ca of the associated apparatus 
Li plus inductance of interconnecting cabling is less than La fo the associated apparatus

5 .  "Simple Apparatus" is a device that will not generate or store more than 1 .2V, 0,1A, 25mW or 20uJ 

Hazardous Location 
Class I , Division 2 
Groups A, B, C, D 
T5 Hazardous (classified) Areas

MiniPurge: Option Code /IS 
Vmax = 30v 
Imax = 350mA 
Ci = 0 Li = 0

Non- Hazardous Location 
(or suitably protected enclosure)

Power Supply

Outputs to relays or 
power contactors

Intrinsically Safe 
Interface Unit

Simple apparatus 
device

Содержание C2N363/600D

Страница 1: ...s C2N36 C2N50 Voltage options 600V 3 phase 480V 3 phase 415V 3 phase 400V 3 phase 380V 3 phase Table of Contents Pre Installation Information 2 3 Storage Instructions 3 Mounting Heater 4 Plumbing Inst...

Страница 2: ...result in serious burns or death Disconnect power supply before performing any work in the enclosure Failure to ground this system may result in death or serious injury Make sure that all water supply...

Страница 3: ...ing quick close valves or solenoid valves it is important to install a hammer arrestor or surge tank close to the point of use to absorb pressure spikes Installation Considerations Maximum operating p...

Страница 4: ...the vertical surface Vertical surface must support 150 lbs or more Optional Leg Kit Use the floor mounting template on the side of the crate to help with alignment Secure heater by bolting each leg t...

Страница 5: ...0 B 3 3 8 86 8 203 8 3 4 222 Optional Fused Disconnect Suggested Location for Power Entrance Provided By Installer LOAD L LOAD R READY TEST FAULT RESET GROUND FAULT TEMPERATURE CONTROLLER R 1 2 3 4 5...

Страница 6: ...tranded machine tool wire from an approved isolating 3 pole switch or circuit breaker NOTICE Make sure the electrical cable is the correct size to carry 100 of the full load current See table for prop...

Страница 7: ...f valve and drain Shutoff valve is installed after pressure and temperature relief valve on outlet if required by local or national plumbing codes If the hot water process is not at the highest point...

Страница 8: ...activate the connected process requiring heated water faucet shower etc then flush the system for 5 minutes to ensure all air is purged from the system NOTICE Failure to bleed air properly will damage...

Страница 9: ...output temperature Setpoint Down Button Decreases output temperature Infinity Key Back to Home page Advance Key Advances through parameter prompts Auto Man Off C r71 Turns Control Loop On Manual Off X...

Страница 10: ...lements if the inlet water temperature is equal to or greater than the temperature set on the digital controller Perform Operational Test No 2 8 A Turn on hot water faucet fixture process The heater s...

Страница 11: ...used disconnect interlocks with enclosure door when energized prohibiting access to a live cabinet Select the FDS option for an additional level of safety and convenience at the heater location T190 H...

Страница 12: ...ery 6 months or more often in areas where hard water sediment is present in the water To clean the Y Strainer 1 Turn the power off at the circuit breaker panel 2 Shut off the installer supplied cold w...

Страница 13: ...al Specifications table in Step 3 for proper requirements 2 Unit is receiving voltage from all 3 phases of the power source A load voltage reading is also helpful 3 Verify the functionality of the flo...

Страница 14: ...Purge gas compressed air inlet fitting here EXP2 Installation Notes 1 Any tubing conduit or fittings connected to the Pressurized Enclosure PE must conform to local codes for flammability ratings 2 A...

Страница 15: ...osure and the protective gas supply The alarm actuator shall be mechanical pneumatic or electrical Electrical alarms and electrical alarm actuators shall be approved for the location in which they are...

Страница 16: ...irements No valves may be fitted between the Expo Technologies system and the alarm switch WARNING Never turn on the power without purging first unless you have proved the interior of the PE is gas fr...

Страница 17: ...larms function correctly Check the Relief Valve and any other Spark Arrestors Remove any debris or corrosion or replace the Spark Arrestor Check the condition of the air supply filter element Clean or...

Отзывы: