4.4 Protective earth conductor connection
Step
Action
Comment
1.
Connect the PE connections on the supply unit, the axis controllers
and the controller
in a star topology
to the PE rail (main earth)
in the switch cabinet (see Figure 4.7).
Tightening torques for PE connection on the device:
M10:
22 Nm
M6:
4.8 Nm
Every device in the axis group
must be earthed!
2.
Also connect the protective earth conductor connections on all
other components, such as mains filter*), mains choke*) etc.
in a
star topology
to the PE rail (main earth) in the switch cabinet.
*) Components are
only required for the
KeDrive D3-DP supply unit.
3.
Please take into account the local and national regulations and
conditions. The minimum cross-section of the protective earth
conductor must comply with the local safety requirements for
protective earth conductors for equipment with high leakage
current.
4.4.1
PE connection according to DIN EN 61800-5-1
The leakage current is > 3.5 mA. This situation results in the following minimum re-
quirements for the protective earth conductor cross-section as a function of the phase
conductor cross-section, as per EN 61800-5-1.
Cross-section of the phase conductors
Minimum cross-section of the corresponding
protective earth conductor
Q ≤ 16 mm
2
Q however at least 10 mm
2
(Cu)
16 mm
2
< Q ≤ 35 mm
2
16 mm
2
Q > 35 mm
2
Q/2
Table 4.13 Protective earth conductor cross-section
NOTE:
During operation with BG4 supply unit connected in parallel, the specific
information about the protective earth conductor connection and cross-
section is to be noted (see Operation Manual KeDrive D3-DP BG3 and BG4,
art. no.: 1804.201B.x)
CAUTION!
Risk of injury due to incorrect wiring!
Carelessness may result in injuries.
The protective earth conductor connection is a safety feature. Therefore, make sure that all
connections have good contact and are sufficiently secure that they cannot come loose.
You will find a wiring example for the axis group in which you will also find detailed infor-
mation about the protective earth conductor connections in Figure 4.22.
35
1 Electrical installation
Operation Manual KeDrive D3-DA BG3 and BG4
1804.200B.1-01 Date: 03/2023
Electrical installation
Содержание KeDrive D3-DA BG3
Страница 1: ...Operation manual Compact multi axis system KeDrive D3 KeDrive D3 DA Axis Controller BG3 and BG4...
Страница 14: ...14 1 Safety Operation Manual KeDrive D3 DA BG3 and BG4 1804 200B 1 01 Date 03 2023 Safety...
Страница 24: ...24 1 Operation Manual KeDrive D3 DA BG3 and BG4 1804 200B 1 01 Date 03 2023...
Страница 66: ...66 1 Operation Manual KeDrive D3 DA BG3 and BG4 1804 200B 1 01 Date 03 2023...
Страница 78: ...78 1 Appendix Operation Manual KeDrive D3 DA BG3 and BG4 1804 200B 1 01 Date 03 2023 Appendix...
Страница 82: ...82 1 Glossary Operation Manual KeDrive D3 DA BG3 and BG4 1804 200B 1 01 Date 03 2023 Glossary...
Страница 83: ...83 1 Operation Manual KeDrive D3 DA BG3 and BG4 1804 200B 1 01 Date 03 2023...