68
Hiperface - Encoder Connections
5
4
3
2
1
10
9
8
7
6
15
14
13
12
11
HIPERFACE
Drive connection X3A
Female SUBD 15 HD
Circular connector on
HIPERFACE encoder.
4
B -
Red
9
B +
Blue
14
DATA -
Pink
15
DATA +
Gray
3
A -
Yellow
8
A +
Green
Shield wire tied to housing
Wire color
13
0V (com)
White
10
+7.5V
Brown
Shield wire tied to housing
which is earth ground.
Encoder pin-out
X3A pin-out channel 1
B -
4
B +
8
DATA -
7
DATA +
6
A -
5
A +
9
GND 11
+7.5V 10
Note: Inner pair shields are tied to 0V (com),
pin 13, not earth ground!
Encoder Card Part Number:
Housing Siz
e ≤ E, 1MF5K8G-FZ49. Housing Size ≥ G 2MF5K8G-FZ39
• Max. Load capacity depending on Voltage Supply
• Max. Load capacity at +7.5 V = 300 mA.
The specified current is reduced by the load current taken from
the second encoder interface X3B interface (see Section 3.3.9).
HIPERFACE Cable
Pre-manufactured Hiperface cables offer the best solution against noise and disturbance while at the same
time saving installation time. The cables come in standard lengths of 5m,10m,15m,20m, 25m, and 30m.
Cable Part Number
00S4809-00xx xx = length in meters, 10 = 10 meters
Mating Connector
0090912-003U
for encoder (solder type)
Running in Conduit
When this cable must be pulled through metallic conduit, it is necessary to over size the conduit!
The
use of a 1 1/2-inch trade size conduit will allow the connectors to pass without removal of the connectors.
Cutting the cable, or removal of the connectors or their housings voids the warranty and will result in
problems with electrical noise after the fact.
Pin No.
Signal
Description
3
A-
signal input A-
4
B-
signal input B-
8
A+
Signal input A+ (absolute track for counter and direction detection)
9
B+
Signal input B+ (absolute track for counter and direction detection)
10
+7.5V
Supply voltage for encoder
13
COM
reference potential for supply voltage
14
DATA -
Data channel RS485
15
DATA +
Data channel RS485
ONLY when the inverter is switched off and the volt-
age supply is disconnected may the feedback con-
nectors be removed or connected!