233
LO - Output Parameters
When one of the output functions in LO05-20 is assigned as Condition 1,
LO30 Data Value 1 is the value which will be evaluated against the LO32
Comparison Level 1 according to the operand LO31 Condition 1.
The setting for LO30 corresponds to the associated Dg parameter.
For example, when LO30 = 2, this corresponds to Dg02 Inverter Status.
If LO31 = ‘=’ and if LO32 = 30, then the output would become active when
the DG02 Inverter State = 30; Error Motor Protection (EOH2).
Determines the operand evaluating LO30 Data Value 1 against the LO32
Comparison Level 1.
The following operands are available according to the table below.
Setting:
Description:
NUM
<
LO30 Less Than LO32
0
<=
LO30 Less Than or Equal to LO32
1
=
LO30 Equal to LO32
2
>=
LO30 Greater Than or Equal to LO32
3
>
LO30 Greater Than LO32
4
< (AbsVal)
Absolute Value of Diagnostic parameter
corresponding to LO30 Less Than the value of
LO32
5
= (AbsVal)
Absolute Value of Diagnostic parameter
corresponding to LO30 Equal to value of LO32
6
> (AbsVal)
Absolute Value of Diagnostic parameter
corresponding to LO30 Greater Than the value of
LO32
7
The value which the LO30 Data Value 1 is compared against for evaluation
according to the operand in LO31 Condition 1.
LO30
Data Value 1
LO31
Condition 1
LO32
Comparison Level 1