The recommended motor rating is for 4/6 pole standard motors. When using motors with different numbers
of poles, the inverter must be dimensioned based on the motor-rated current. Contact the manufacturer
for special frequency motors.
The power rating of the inverter must be de-rated for operation above 3,300 ft (1000 m). Reduce the rated
power 1% for each additional 330 ft (100 m). The maximum elevation for operation is 6,560 ft (2000 m).
Inverter Size
13
14
15
16
16
17
17
18
19
Max Motor Power
[hp]
7.5
10
15
20
15
25
18.5
30
40
Housing Size
E
E
E
G
H
G
H
H
H
Unit Hardware
B
B
B
B
B
B
B
B
B
Input Ratings
Supply voltage [V]
305...528 ±0 (480 V Nominal voltage
)
Supply voltage frequency [Hz]
50 / 60 +/- 2
Input phases
3
3
3
3
3
3
3
3
3
Rated input current 400VAC [A]
17
23
31
43
43
55
55
65
66
(UL) Rated input current 480VAC [A]
15.4
19.6
27.3
35
35
44
44
52
57
UL minimum wire gauge
2)
[awg]
24
24
24
16
8
16
6
12
12
UL maximum wire gauge
2)
[awg]
10
10
10
4
0
4
1/0
0
0
Output Ratings
Rated output power [kVA]
8.3
11
17
23
23
29
29
35
42
Rated motor power [kW]
5.5
7.5
11
15
15
18.5
18.5
22
30
Rated output current 400VAC [A]
12
16.5
24
33
33
42
42
50
60
(UL) Rated output current 480VAC [A]
11
14
21
27
27
34
34
40
52
Peak current (30 seconds)
3)
[A]
21.6
29.7
36
49.5
49.5
63
63
75
90
Over current fault (E.OC) trip level [A]
25.9
35.6
43.2
59.4
59
75.6
75
90
108
Output voltage [V]
3 x 0…Vsupply
Output frequency [Hz]
Generally 0 to 599Hz (limited by carrier frequency)
Rated switching frequency
4)
[kHz]
8
8
4
8
16
4
8
8
8
Maximum switching frequency [kHz]
16
16
16
16
16
16
16
16
16
Power loss at rated operation
5)
[W]
250
320
350
310
490
360
470
610
540
Stall current at 4kHz [A]
12
16.5
24
33
41.91
42
42
60
60
Stall current at 8kHz [A]
12
16.5
16
21.5
33
21.5
42
50
54
Stall current at 16kHz [A]
12
10
10
9.5
19.8
-
25.2
30
36
Braking Circuit
Min. braking resistance [Ohm]
39
36
36
19
19
19
19
9
9
Typ. braking resistance [Ohm]
100
85
56
39
39
28
28
22
16
Max. braking current [A]
21
21
21
40
40
40
40
90
90
Installation Information
Max. shielded motor cable length
7)
[ft]
300
330
330
330
330
330
330
330
Tightening torque for power terminals [in lb]
4.5
4.5
11
11
35
11
35
35
35
Environmental
Max. heat sink temperature TOH [°C]
90°C / 194°F
Storage temperature [°C]
-25...70 °C / -13…158°F
Operating temperature [°C]
-10...45 °C / 14…113°F
Housing design / protection
Chassis/IP20 /Pollution Degree 2
Relative humidity
max. 95% without condensation
Approvals
Tested in accordance with…
EN 61800-3 /UL508C
Standards for emitted interference
EN 55011 Class B/EN 55022 Class A
Standards for noise immunity
IEC 1000-4-2 / -3 / -4 / -5/ -6
Climatic category
3K3 in accordance with EN 50178
*Additional sizes available
2.5 Technical data 480V (size 13 to 28)*