TECHNICAL DESCRIPTION
ULTRAFLOW
®
54 DN150-250
5512-876 GB/04-2012/Rev. F1
21
7.3
Straight inlet
ULTRAFLOW
®
54 requires neither straight inlet nor outlet in order to fulfil the Measuring Instruments Directive
(MID) 2004/22/EC and EN 1434:2007. A straight inlet section will only be necessary in case of heavy flow
disturbances before the meter. We recommend following the guidelines of CEN CR 13582.
Optimal position can be obtained by taking the below-mentioned installation methods into consideration:
Figure 11
For general information concerning installation see CEN report
DS/CEN/CR 13582, Heat meter installation.
Instructions in selection, installation and use of heat meters
.
7.4
Operating pressure
In order to prevent cavitation the back pressure at ULTRAFLOW
®
54 must be min. 1.5 bar at q
p
and min. 2.5 bar at
q
s
. This applies to temperatures up to approx. 80°C.
For further information on operating pressure see
paragraph 8.7
A
Recommended flow sensor position
B
Recommended flow sensor position
C
Unacceptable position due to risk of
air build-up
D
Acceptable in closed systems.
Unacceptable position in open systems
due to risk of air build-up in the
system.
E
A flow sensor should not be placed
immediately after a valve, except for
block valves (ball valve type),
which must be fully open when not
used for blocking
F
A flow sensor must never be placed
on the inlet side of a pump
G
A flow sensor should not be placed after
a two-level double bend