KACO blueplanet 3.0 NX1 M2 KACO blueplanet 3.7 NX1 M2 KACO blueplanet 4.0 NX1 M2
KACO blueplanet 5.0 NX1 M2
Page 16
4.2
Enabling functions
HINWEIS
You will find a description of the individual functions starting from chapter 4.3 at page 17. More
parameters will also be continuously added in future firmware versions. Therefore, please refer to the PDF
version of this application note to view important additions.
<Communication device> menu opened.
1. Select <Activate/Deactivate Functions> under <Settings for> and <select Inverter>.
2. Toggle the desired function after setting the respective parameter (see references).
-
Activate Power Control (See Chapter 2.5 on page 11)
-
70 % active Power Limit (Details see Chapter 6 on page 28)
-
Active Power Ramp (See Chapter 4.8 on page 19)
-
P(U) (See chapter 4.10 on page 21)
-
P(f) (See chapter 4.9 on page 20)
-
Reactive Power Control (See chapter 4.11 on page 22)
-
LVRT (Low Voltage Ride Through) - Describes the requirement that generating plants must continue to operate
through short periods of low grid voltage and not disconnect from the grid.
-
Trip Overvoltage (10min Average) – Protection function
-
Islanding detection - protective function
-
PE wire detect – Ground Protection function
-
MPPT parallel operation (See Manual – Chapter 8.5.3)
-
Active power increase in the event of over frequency P(f)
3. Transfer the selection with <OK>. The unit then restarts with the desired range of functions
»
The desired functions are permanently set.
Fig. 54.
Select inverter
Fig. 55.
Activate/Deactivate Functions
Fig. 56.
Switching the required functions