Page 23
KACO blueplanet 3.0 NX1 M2 KACO blueplanet 3.7 NX1 M2 KACO blueplanet 4.0 NX1 M2 KACO blueplanet 5.0 NX1 M2
4.11.1
Settings for “Cos-Phi Constant “
Note:
In cos phi -constant mode, the
specified power factor is fixed by the inverter.
In doing so, the reactive power level is set in
line with Q=P*tan ϕ as a function of the
power that continuously generates the
specified power factor.
Open menu <Setting for>.
1.
Select <Cos-Phi Constant Setting> menu.
2. Set fixed displacement factor.
3. Select phase.
4. <Confirm> all settings.
» Cos-phi constant defined.
Fig. 81.
Select Cos-phi constant
settings
Fig. 82.
Define cos-phi constant
4.11.2
Settings for “Q Constant “
Note:
The setpoint of the reactive power can
be adjusted depending on the set maximum
apparent power.
Open menu <Setting for>.
1.
Select <Q constant Setting> menu.
2. Set Q in %
3. Select the type of phase shift via drop-
down field.
4. <Confirm> all settings.
» <Q constant> defined.
Fig. 83.
Select Q Constant Settings
Fig. 84.
Set reactive Power Setpoint