Page 17
KACO blueplanet 3.0 NX1 M2 KACO blueplanet 3.7 NX1 M2 KACO blueplanet 4.0 NX1 M2 KACO blueplanet 5.0 NX1 M2
4.3
Connection Conditions
Note:
The suitable voltage and frequency
range for grid operation can be set in
accordance with the requirements of the local
grid operator.
<Setting for>-Menu opened.
1.
<Connection Settings> opened.
2.
Set parameters for min./max. start
voltage and start frequency.
3.
<Confirm> all settings.
» Grid parameters set.
Fig. 57.
Connection Conditions
Fig. 58.
Set connection conditions
4.4
Trip Voltage Settings
Note:
There are three threshold values for
overvoltage and undervoltage protection. The
first threshold value specifies the lower
range. The middle threshold range is freely
adjustable. The third threshold value
indicates the upper range.
Open menu <Settings for>.
1.
Select <Trip Voltage Settings>.
2.
Set min. and max. shutdown time with
associated voltage for each phase.
3. <Confirm> all settings.
» Voltage protection defined.
Fig. 59.
Select Trip Voltage Settings
Fig. 60.
Define voltage range and
switch-off times