4
1
2
3
4
Activation threshold
with overfrequency
50.2 – 70 (Hz)
Activation threshold
with underfrequency
40 – 45 (Hz)
1 Set frequency thresholds for activating the power limitation with
overvoltage.
2 Set the frequency thresholds for activating the power limitation
with undervoltage.
4
1
2
3
4
Output gradient limita-
tion increase & Output
gradient limitation de-
crease
1 - 65534 [% / min]
F
Specify the increasing and decreasing output gradient.
4
1
2
3
4
Power reduction P(U)
NOTE: To prevent the device from shutting down due to overvoltage
protection, the active power can be regulated in addition to reactive
power control in order to reduce the active power feed-in whereby
the output voltage is reduced.
4
1
2
3
4
P(U) operation mode
Off | On
F
Activate the control process.
Off: Deactivates dynamic grid support using dynamic reactive current.
Dynamic grid support remains active on account of immunity to inter-
ference.
4
1
2
3
4
Reference power
Actual power |
Nominal power
F
Select the power-dependent control method.
4
1
2
3
4
Evaluated voltage
Maximum phase
voltage | Positive
phase sequence
voltage
F
Select the voltage to be rated.
Specifies which voltage is evaluated in a three-phase system.
4
1
2
3
4
Hysteresis mode
Off | On
NOTE: Hysteresis mode affects the shutdown response of P(U).
F
Activate the mode.
4
1
2
3
4
Deactivation gradient
0 – 65534 [% / min]
F
Set the gradients for the power limitation.
4
1
2
3
4
Deactivation time
0 – 60000000 [ms]
F
Specify the time for voltage reduction.
4
1
2
3
4
Output gradient limita-
tion increase & Output
gradient limitation de-
crease
1 - 65534 [% / min]
F
Specify the increasing and decreasing output gradient.
4
1
2
3
4
Settling time
200 – 120000 [ms]
F
Specify the settling time.
4
1
2
3
4
Active curve
1 - 5
F
Select active curve.
NOTE: Up to 5 characteristic curves can be configured independently
and one of them can be activated for regulation each time.
Kaco blueplanet 29.0TL3
Page 52
EN