7.6.5
Connecting the PV generator
DANGER
Risk of fatal injury due to electric shock!
Severe injury or death will result if the live connections are touched. When there is sunlight present on the
PV generator, there is DC voltage on the open ends of the DC cables.
›
Only touch the PV generator cables on the insulation. Do not touch the exposed ends of the cables.
›
Avoid short circuits.
›
Do not connect any strings with a ground fault to the device.
CAUTION
Damage to the PV generator in case of faulty configuration of the DC connector.
A faulty configuration of the DC connector (po/-) causes equipment damage in the DC connection if
it is connected permanently.
›
Please check polarity (+/-) of the DC connector before connecting the DC generator.
›
Before using the solar modules, check the vendor’s calculated voltage values against those actually
measured. The DC voltage of the PV system must not exceed the maximum no-load voltage at any
time.
Connecting the PV generator
↻
PV generator is dimensioned according to the performance characteristics of
the unit.
1 Loosen the cable fittings [ W_36
(
M32 )].
2 Remove the outer cladding of the DC cables.
3 Pass the DC cables through the cable fittings into the connection compartment
[
Ø
15 - 21 (M32) mm ].
4 Strip the insulation from the DC cables.
5 Fit DC lines with an ring cable lug [max. width b 20 mm].
6 Remove the protection against contact from the PV+ and PV- terminal.
7 Screw the cable ends of the PV generator onto the DC connection according to
the polarity of the battery [ T_TX35 / 15 - 22 ].
8 Check secure fit of all connected cables.
9 Remove the protection against contact from the PV+ and PV- terminal.
10 Tighten the cable fittings [ W_36 / 4 Nm].
»
The device is connected to the PV generator.
PV +
PV-
20 mm
20 mm
Ø 9 mm
Fig. 29:
Connection to Basic + M
version
20 mm
20 mm
Ø 9 mm
PV +
PV-
Fig. 30:
Connection to S version
Connecting the PV generator
↻
PV generator is dimensioned according to the performance characteristics of
the unit.
1 Remove protective cap from the DC connection plugs required.
NOTE: For each plug connector pair, the power output can be connected in re-
lation to the string fuse size used.
2 Connect the PV generator to the DC plug connectors on the underside of the
unit according to the polarity of the PV generator.
NOTE: Meet the requirements of protection class IP65 by closing the unused
plug connectors with protective caps.
»
The device is connected to the PV generator.
DC+
DC-
Fig. 31:
Connection to XL version
Kaco blueplanet 29.0TL3
Page 27