Country-
spec. Set-
tings
Men
u
level
Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Parameters
F
Press the
Right arrow button
or
Enter button
.
NOTE: The device does not display the "Parameters" menu in the
standard configuration. To display the Parameters menu:
1 Open the menu.
2 Simultaneously hold down the
Up
and
Down buttons
for sev-
eral seconds.
4
1
2
3
4
Password protection
Status
On/Off
NOTE: Opportunity to set password protection.
F
Selecting "yes" initiates a password request for the entire menu
item:
Parameters
.
4
1
2
3
4
Country
NOTE: This option influences the country-specific operating settings of
the device. Please consult KACO service for further information.
1 Enter the four-digit password using the 4-way button. The password
is unit-specific.
2 Confirm the entry with the
Enter
button.
3 Set the desired country setting.
CH, DE, ES,
FR, GB, GR,
IT, JO, JP,
LU, TH, ZA
4
1
2
3
4
Grid type/guideline
F
Select the grid type for the device’s installation location.
UD
4
1
2
3
4
Nominal grid voltage
F
Set the specified grid voltage for the site where the unit is used
(please contact KACO Service)
4
1
2
3
4
Grid parameter
F
Open the menu: Press the
Right arrow button
or
Enter
button
.
AT, BG, CZ,
FR-OLD,
FR-VFR13,
FR-VFR14,
IE, JP, NL,
PL, PT, TR,
TW, UD
4
1
2
3
4
Overvoltage shutd. Av-
erage value over ten
minutes
1 Specify the shutdown threshold for overvoltage shutdown.
ð
The 10-minute average for the measured voltage as per
EN50160 is used.
2 Set period from occurrence of the fault to shutdown of the device.
BE CH-NS
CY DE-NS
DK LU-NS
4
1
2
3
4
Overvoltage shutd. Av-
erage value over ten
minutes Password pro-
tection
1 Activate or disable password protection.
2 Specify the shutdown threshold for overvoltage shutdown.
ð
The 10-minute average for the measured voltage as per
EN50160 is used.
3 Set period from occurrence of the fault to shutdown of the device.
AT FR-OLD
FR-VFR13
FR-VFR14
JP-50HZ
JP-60HZ
UD
4
1
2
3
4
Voltage drop
NOTE: The voltage drop between the device and the feed-in meter is
added to the limit value that was set for grid shutdown according to
EN 50160. The limit value can be set to 0-11 Volt increments.
F
Specify the shutdown value for the voltage drop (0-11 Volt).
BE CH-NS
CY DE-NS
DK LU-NS
4
1
2
3
4
Switch-off volt.
NOTE: The device is equipped with redundant 3-phase monitoring. If
the grid voltage exceeds or drops below the configured values, the
device switches off. The minimum switch-off threshold can be set in
1 Volt increments.
1 Configure the switch-off values for undervoltage and overvoltage.
2 Where applicable, set period from occurrence of the fault to shut-
down of the device.
Kaco blueplanet 29.0TL3
Page 41
EN