Country-
spec. Set-
tings
Men
u
level
Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Powador-protect
Auto | On | Off
NOTE: Configures the support for grid shutdown by a Powador-protect
connected to the digital input of the device.
↻
Auto/On: A Powador-protect is operating in the photovoltaic sys-
tem and is connected to the device at the digital input/output.
F
Set the operating mode for Powador-protect.
Auto: The device automatically detects a Powador-protect integrated
into the photovoltaic system.
On: The digital signal of the Powador-protect must be present at the di-
gital input of the device for the device to begin feed-in.
Off: The device does not check whether a Powador-protect is integrated
into the PV system.
4
1
2
3
4
Iso.resistor
F
Set threshold value (in 1kOhm increments) at which the insulation
monitor reports a fault.
4
1
2
3
4
Power reduction P(f)
NOTE: The unit supports the internal power factor correction after
P(f).
1 Open the menu: Press the
Right arrow button
or
Enter
button
.
Note: All the parameters are configurable here and via the WEB in-
terface
Configuration via web user interface [See sec-
Not for IL,
IT
4
1
2
3
4
P(f) operation mode
Off | Mode 1 |
Mode 2
NOTE: More detailed information can be found in
F
Specify the operation mode.
4
1
2
3
4
Threshold activated
45 Hz – 70 Hz
F
Specify activation threshold (if mode 1 or mode 2 is active, this menu
option is displayed permanently for IT and IL!)
NOTE: The function is activated if the activation threshold is exceeded.
In mode 2 this value also serves as a deactivation threshold.
4
1
2
3
4
Threshold deactivated
Min. 45 Hz – 61,5 Hz
Max. 45 Hz – 70 Hz
NOTE: If the grid frequency is within the deactivation range for the
duration of the deactivation time, then the function is deactiv-
ated.
1 Specify deactivation threshold (if mode 1 or mode 2 is active, this
menu option is displayed permanently for IT and IL!).
Not for IL,
IT
4
1
2
3
4
Deactivation time
F
Specify time for power reduction (if mode 1 is active)
4
1
2
3
4
Gradient
F
Set gradient of power limitation function with increasing frequency
in % / Hz. The percentage value is based on the rated frequency (if
mode 1 or mode 2 is active, this menu option is displayed perman-
ently for IT and IL!)
4
1
2
3
4
Intentional delay
F
Set the power limitation delay in seconds (if mode 1 or mode 2 is act-
ive; this menu option is displayed permanently for IT and IL!).
4
1
2
3
4
Settling time
F
Set the power reduction delay in seconds (if mode 1 or mode 2 is act-
ive; this menu option is displayed permanently for IT and IL!).
4
1
2
3
4
Rise Outg. grad. & Fall.
Outg. grad.
F
Specify output gradient increase and decrease in
0
/
00
(per thousand).
4
1
2
3
4
Deact. grad.
F
Specify deactivation gradient in
0
/
00
(per thousand) /minute (if mode "1" or mode "2" is active. This
menu option is displayed permanently for IT and IL!).
Kaco blueplanet 29.0TL3
Page 44
EN