11.3
PROGRAMMING OPTIONS IN DETAIL
11.3.1
Zone 1 Fence Voltage Alarm Level (01xx#)
Sets the voltage below which the zone alarm will occur. If the fence voltage
measured at the return “R” loop terminal falls below this level for more
than the Missed pulse count a fence alarm (zone 1) will occur. The value is
set directly, not via a table.
For example to set a threshold of 25V enter: 0 1 2 5 #
Setting this option to 0 effectively turns off fence voltage monitoring.
Warning: Setting this level to higher than the normal running voltage of the
fence will result in continuous fence alarms.
Value (x)
Alarm Level
Minimum
0
0.0 V
Default
20
20 V
Maximum
40
40 V
11.3.2
Missed Pulse Count (06xx#)
This option enables the pulse count to be varied from the default (3). This
is the number of bad or missing pulses that are counted before the alarm
occurs.
NOTE:
The lower this option is set the more likely you are to get false
alarms.
The value is set directly. For example to set a threshold of 2 bad or missing
pulses enter: 0 6 0 2 #.
Value (x)
Missed Pulses
0
1
1
1
2
2
3
3
Содержание ZLM1
Страница 1: ...Single Zone Low Voltage Monitor ZLM1 User Manual JVA TECHNOLOGIES www jva fence com...
Страница 5: ...Page 5 JVA ZLM1 Manual Contents...
Страница 11: ...Page 11 Introduction JVA ZLM1 Manual...
Страница 50: ...Technical Information Page 50 JVA Technologies Pty Ltd www jva fence com...
Страница 51: ...Page 51 Technical Information JVA ZLM1 Manual DEALER...
Страница 52: ...www jva fence com...