CONSTRAINTS
•
Any energiser used with the ZLM1 must comply with IEC60335.2.76
electrical safety standard. All JVA energisers under 18J output are suit
-
able.
•
Energisers with a negative voltage are not suitable
•
The energiser output pulse energy must not exceed 18 Joules
• The maximum series resistance of the fence wire loop which can be
accurately monitored is 5000 Ohms
•
Since the ZLM1 is a relatively new addition to the JVA Z series, older
versions of TCP/IP adaptors, GPIO, Wi-Fi and GSM gateways may not
be compatible with it. Please contact your distributor or store to get
the latest versions.
•
The JVA LCD keypad (PTE0210) requires version 2.12 or later firmware
to operate with a ZLM1, the keypad firmware can be viewed by at pow
-
er up or by pressing *9# on the keypad.
• Perimeter Patrol version 5.2.2 or later is required to operate with a
ZLM1