The location of the rack must provide sufficient space to accomodate the depth of the services gateway.
The chassis is 24.5 in. (62.2 cm) deep.
•
The rack must be strong enough to support the weight of the fully configured device, up to 220 lb
(100 kg). If you stack five fully configured devices in one rack, it must be capable of supporting up to
1100 lb (500 kg).
Spacing of Rack Mounting Bracket Holes for the SRX5600 Services Gateway
The services gateway can be mounted in any rack that provides holes or hole patterns spaced at 1 U (1.75
in.) increments. The mounting brackets used to attach the chassis to a rack are designed (as per EIA-310-D
specifications) to fasten to holes spaced at those distances.
Connection to Building Structure for the SRX5600 Services Gateway Rack
Always secure the rack to the structure of the building. If your geographical area is subject to earthquakes,
bolt the rack to the floor. For maximum stability, also secure the rack to ceiling brackets.
SRX5600 Services Gateway Cabinet Size and Clearance Requirements
The minimum size cabinet that can accommodate the device is 482 mm wide and 800 mm deep. A cabinet
larger than the minimum requirement provides better airflow and reduces the chance of overheating. To
accommodate a single device, the cabinet must be at least 13 U high. If you provide adequate cooling air
and airflow clearance, you can stack five devices in a cabinet that has at least 48 U (84 in. or 2.13 m) of
usable vertical space.
The minimum front and rear clearance requirements depend on the mounting configuration you choose.
The minimum total clearance inside the cabinet is 30.7 in. between the inside of the front door and the
inside of the rear door.
165
Содержание SRX5600
Страница 1: ...SRX5600 Services Gateway Hardware Guide Published 2020 02 14 ...
Страница 23: ......
Страница 105: ...LEDs 106 ...
Страница 114: ...Figure 51 SRX5K MPC g030309 MPC empty 115 ...
Страница 124: ...Port and Interface Numbering 125 ...
Страница 130: ...Port and Interface Numbering 131 ...
Страница 156: ......
Страница 183: ...Table 54 RJ 45 Connector Pinout for the AUX and CONSOLE Ports continued Description Signal Pin Clear to Send CTS 8 185 ...
Страница 185: ......
Страница 193: ...Figure 84 Installing the Front Mounting Hardware for a Four Post Rack or Cabinet 196 ...
Страница 239: ......
Страница 285: ...c Upload the configuration to RE2 from the USB device 288 ...
Страница 372: ...5 CHAPTER Troubleshooting Hardware Troubleshooting the SRX5600 377 ...
Страница 373: ......
Страница 407: ......
Страница 420: ...423 ...
Страница 423: ...Restricted Access Area Warning 426 ...
Страница 430: ...433 ...
Страница 443: ...Jewelry Removal Warning 446 ...
Страница 446: ...Operating Temperature Warning 449 ...
Страница 456: ...DC Power Disconnection Warning 459 ...
Страница 460: ...DC Power Wiring Sequence Warning 463 ...
Страница 463: ...DC Power Wiring Terminations Warning 466 ...
Страница 466: ...DC Power Disconnection Warning 469 ...
Страница 470: ...DC Power Wiring Sequence Warning 473 ...
Страница 473: ...DC Power Wiring Terminations Warning 476 ...