Figure 98: Proper Load Balancing for JNP10K-PWR-DC2 Power Cables on an MX100016
g100690
WARNING:
Ensure that the power cords do not block access to router components
or drape where people can trip on them.
18. Set the three dip switches to set the inputs and whether the power supply is running at 3000 W or at
5500 W. Set input 1 (IP0 to enable A0 and B0. Set input 2 (IP1 to enable A1 and B1. Set the H/L to
the on position for 5500 W and set it to the off position for 3000 W. See
Set both enable switches to the on position when using both source inputs. When not using source
redundancy, set the unused source to the O (off) position. The LED turns red and indicates an error if
a source input is not in use and the enable switch is | (on).