Table 19: LEDs on a DC Power Supply in an MX10016 (continued)
Description
State
Color
LED
The power supply has failed and must be replaced.
On Steadily
Red
FAULT
•
The power supply is functioning normally.
•
Only one input is powered and the enable switch
for the input that is not powered is set to ON. See
“Connecting DC Power to an MX10016” on
for more information about the enable
switches.
Off
Unlit
NOTE:
If the INP1 or INP2 and the PWR OK LED are unlit, the power cords are not installed
properly or the power supply has failed.
If the INP1 or INP2 LED is lit green and the PWR OK LED is unlit, the power supply is not installed
properly or the power supply has an internal failure.
If the FAULT LED is blinking, add a power supply to balance the power demand and supply.
JNP10K-PWR-DC2 Power Supply LEDs
A JNP10K-PWR-DC2 power supply module has four LEDs on its faceplate: 1, 2, OK, and the symbol for
fault, !. These LEDs display information about the status of the power supply. See
.
73
Содержание MX10016
Страница 1: ...MX10016 Universal Routing Platform Hardware Guide Published 2019 10 15 ...
Страница 19: ......
Страница 86: ......
Страница 123: ......
Страница 153: ......
Страница 239: ...Figure 118 Moving the MX10016 Using a Mechanical Lift g100421 242 ...
Страница 240: ...5 CHAPTER Troubleshooting Hardware Restoring Junos OS 245 Alarm Messages 249 ...
Страница 241: ......
Страница 249: ......
Страница 277: ...Restricted Access Warning 281 ...
Страница 292: ...Jewelry Removal Warning 296 ...
Страница 295: ...Operating Temperature Warning 299 ...
Страница 304: ...DC Power Disconnection Warning 308 ...
Страница 308: ...DC Power Wiring Sequence Warning 312 ...
Страница 311: ...DC Power Wiring Terminations Warning 315 ...
Страница 320: ...Translation The emitted sound pressure is below 92 dB A per GR63 CORE 324 ...