Power On the G10 CMTS
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
JUNOSg 3.0 G10 CMTS Hardware Guide
124
Table 40: Power Supply LEDs
4.
Replace the power supply faceplate by aligning its four ball studs with the four power
supply faceplate clips and pressing the faceplate towards the chassis until it snaps into
place.
5.
Ensure that the fan tray LEDs (two in front, one in rear) are not illuminated (see Figure 4
on page 11 and Figure 7 on page 14 for the location of these LEDs). If any fan tray LED is
illuminated red, one or more fans in that tray has failed and you must replace the entire
tray (see “Replace a Fan Tray” on page 162).
POWER
FAULT
Potential Meaning
Action
Green
Not illuminated
Normal operation
None
Green
Red
Over-temperature
!
Check that fan trays are operational (see step 5
on page 124).
!
Ensure all empty module slots and power supply
bays contain air management modules, panels,
and filler panels.
!
Ensure air intakes and exhaust are not blocked.
Green
Red
Over-current or over power limit condition
Ensure that the correct number of power supplies are
installed to support the CMTS configuration.
Not illuminated
Red
Voltage input failure
Ensure that the external power sources are operating
within specification.
Not illuminated
Not illuminated
!
Power supply not installed correctly.
!
No input power and no DC output from
other power supplies to illuminate
FAULT
LED.
!
Power down the G10 CMTS and reinstall the
power supply as described on “Install Power
Supplies” on page 101. If power supply
redundancy is implemented, you can replace a
power supply without powering down the
system.
!
Ensure that the external power sources are
switched on.
If the
POWER
LED is not illuminated, the
FAULT
LED can be
illuminated red only if the DC output voltage is present
from other power supplies.
To minimize the risk of damage to the G10 CMTS, you
should replace a failed fan tray as soon as possible to
ensure that proper air ventilation occurs throughout the
chassis.
Содержание G10 CMTS
Страница 8: ... JUNOSg 3 0 G10 CMTS Hardware Guide viii ...
Страница 18: ... JUNOSg 3 0 G10 CMTS Hardware Guide 2 ...
Страница 34: ...G10 CMTS Hardware Overview JUNOSg 3 0 G10 CMTS Hardware Guide 18 ...
Страница 46: ...DOCSIS Module JUNOSg 3 0 G10 CMTS Hardware Guide 30 Figure 12 DOCSIS Module Front Panel HotSwap ...
Страница 55: ... Hardware Component Overview Chassis Control Module 39 Figure 15 Chassis Control Module Front Panel Eth0 ...
Страница 72: ...Chassis Rear Modules JUNOSg 3 0 G10 CMTS Hardware Guide 56 Figure 21 Hard Disk Module Rear Panel C O M Eth ...
Страница 82: ... JUNOSg 3 0 G10 CMTS Hardware Guide 66 ...
Страница 112: ...Rack Mounting JUNOSg 3 0 G10 CMTS Hardware Guide 96 Figure 25 Air Flow Through Chassis ...
Страница 116: ...Rack Mounting JUNOSg 3 0 G10 CMTS Hardware Guide 100 Figure 29 Rack Fully Populated with Three G10 CMTS Chassis ...
Страница 118: ...Install Power Supplies JUNOSg 3 0 G10 CMTS Hardware Guide 102 Figure 30 Power Supply Installation 1 2 ...
Страница 138: ...Connect to Power Sources JUNOSg 3 0 G10 CMTS Hardware Guide 122 Figure 39 DC Power Transition Module ...
Страница 148: ... JUNOSg 3 0 G10 CMTS Hardware Guide 132 ...
Страница 156: ...Upstream RF Measurement JUNOSg 3 0 G10 CMTS Hardware Guide 140 ...
Страница 188: ... JUNOSg 3 0 G10 CMTS Hardware Guide 172 ...
Страница 196: ...Radio Frequency RF Specifications JUNOSg 3 0 G10 CMTS Hardware Guide 180 ...
Страница 202: ...EIA Channel Plans JUNOSg 3 0 G10 CMTS Hardware Guide 186 ...
Страница 203: ... 187 Part 5 Index Index on page 189 ...
Страница 204: ... JUNOSg 3 0 G10 CMTS Hardware Guide 188 ...
Страница 209: ... Index 193 Index V ventilation 69 89 95 101 124 161 162 167 video servers 7 voltage power supply 27 ...
Страница 210: ... Index JUNOSg 3 0 G10 CMTS Hardware Guide 194 ...